Goodman AMVS96U Service And Troubleshooting page 10

Single stage variable speed ultra-low nox gas furnaces and accessories
Table of Contents

Advertisement

SYSTEM OPERATION
24 VOLT THERMOSTAT WIRING
NOTE: Low voltage connections can be made through either
the right or left side panel. Wire routing must not interfere
with circulator blower operation, filter removal, or routine
maintenance.
A 40 V.A. transformer and an integrated electronic control are
built into the furnace to allow use with most cooling equipment.
Consult the wiring diagram, located in the Technical Manual
or on the blower door for further details of 115 Volt and 24
Volt wiring.
The single stage furnace will have a "W" terminal and will use
a single stage thermostat. The following drawing illustrates
the typical field wiring for a heat only single stage system and
a single stage heating/single stage cooling system. Refer to
the following figures for proper connections to the integrated
control module.
EXTREMELY IMPORTANT: This system does not contain
an O wire input (reversing valve signal). If a heat pump is
installed, the thermostat should be setup for single stage
heat/single stage cool installs ( W= Heat Call and Y = Cool
Call). Setting thermostat for heat pump control will result in
incorrect performance.
Quick Start Guide
1) Connect all necessary thermostat wires to the
thermostat connector on the furnace control (only
available connections on the furnace are R & C for
power, Y for Cooling Calls, W for Heating Calls, G for
Fan Calls, Dehum for Dehumidification Calls. Furnace
will control staging of indoor unit and outdoor unit
automatically based on these inputs).
2) Make sure thermostat is set to single stage heat / single
stage cool mode. When a cool call is given, 24VAC
should be applied to the Y terminal (G will have 24VAC
as well if a G wire is installed). When a heat call is given
24VAC should be applied to the W terminal (G may
have 24VAC as well if a G wire is installed). Even if a
heat pump is installed, do not setup the thermostat in
heat pump mode. Single stage heat / single stage cool
mode is all that is required for all applications. See rest
of manual for any exceptions. Do not setup thermostat
in multi stage mode either, it is not necessary.
3) For communicating 2 stage AC/HP or inverter AC/
HP outdoor units, connect the 1&2 wires between the
indoor and outdoor unit. It is recommended for 2 stage
applications that a separate transformer be installed
in the outdoor unit to provide 24VAC to the outdoor
control. R&C can be used between the indoor and
outdoor in 2 stage AC application but only if there isn't
already a transformer installed in the outdoor unit.
4) Turn on power to Indoor and Outdoor units
5) Charging outdoor unit: Provide a cooling call (Y or
Y+G) – this initial cooling call after the power is turned
on will run the outdoor unit at full capacity until the call
is removed. Use this mode for charging. If system is
running low stage cooling just cycle power and provide
a cool call again to ensure full capacity cooling.
10
6) System Testing: Download the CoolCloudHVAC phone
application (see pages 31 and 32)and use it to test all
operations of both indoor and outdoor units.
7) Confirm thermostat heat (W or W+G) and cool (Y
or Y+G) function properly and the system is turning
on in the correct mode. The internal algorithms will
constantly be adjusting the staging times / cooling
capacities based on load changes to the space.
NOTE: If a heat pump is installed it will be treated as a
priority heat for a W call. To test gas heat only, without
waitng for the system to stage between the heat pump
and furnace, disconnect communications between the
indoor and outdoor unit before running the heating test.
Control System – General Information
The furnace contains internal logic to control equipment
staging. An adjustable target runtime is available (range from
1 to 240 minutes) and set through the appropriate system
menu. The system will constantly be adjusting staging in an
effort to satify the thermostat call for cooling (Y only) or heating
(W Only) as close to the set target runtime as possible. See
information below for setting options.
Comfort Setting Menu (CFS): There are 6 options
available in the Comfort Setting Menu which impacts both
the System Target Runtime and Dual Fuel Operation. Dual
Fuel operation adjustments only apply if a communicating
heat pump is installed. Comfort Setting Options 1 – 5 have
set values for the System Target Runtime and option
6 enables additional menus to customize all comfort
settings. See list below for the System Target Runtimes
associated with the first 5 Comfort Settings. These first
5 options are setup to help satisfy the thermostat slower
or faster based on the selection where option 1, with a
10 minute Target Runtime, is attempting to satisfy much
faster than option 5, with a 30 minute Target Runtime.
System Target Runtime:
Comfort Setting Option 1) 10 Minute System Target
Runtime
Comfort Setting Option 2) 15 Minute System Target
Runtime
Comfort Setting Option 3) 20 Minute System Target
Runtime
Comfort Setting Option 4) 25 Minute System Target
Runtime
Comfort Setting Option 5) 30 Minute System Target
Runtime
Dual Fuel Adjustment: This system will automatically
determine if the heat pump is capable of satisfying the
thermostat in the selected System Target Runtime. If the
heat pump is unable to satisfy in the selected time, dual
fuel settings will determine how many attempts should
be given to the heat pump before temporarily locking it
out and using the furnace. These dual fuel settings also
determine at what time the system should remove the

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents