Toshiba MMY-MAP0726FT6P-UL Installation Manual page 8

Table of Contents

Advertisement

Available languages

Available languages

Discharge side gas piping / Liquid piping
▼ Figure 1
Correct
Header unit
A
Follower unit
B
Follower unit
C
Suction side gas piping
▼ Figure 3
Correct
Header unit
A
Follower unit
B
Follower unit
C
• When attaching a Y-shaped branch unit for the outdoor unit connection piping kit, attach it level with the
ground (Be sure not to exceed ±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no
restriction for its angle.
(Horizontal line)
Within ±15 degrees
A
(A arrow view)
B
• In case of using the Y-shaped branching joint for connecting between
outdoor units (Discharge gas joint and Suction gas joint), please keep
the straight part of at least 19.7" (500mm) at the inlet.
13-EN
1122001001-2_EN-FR.indb 7
1122001001-2_EN-FR.indb 7
▼ Figure 2
Incorrect
Header unit
A
Follower unit
B
Follower unit
C
Incorrect
To the indoor unit
[Inverse connection of a gas-side branch unit]
▼ Figure 4
Incorrect
Header unit
A
Follower unit
B
Follower unit
C
To gas-side branch unit
At a level position
(Horizontal line)
Do not connect
Within ±15
a branch unit
degrees
vertically.
(B arrow view)
– 7 –
When drawing pipes downward
▼ Figure 5
Incorrect
Header unit
A
Follower unit
B
Suction gas joint
Vertical line
Suction gas joint
A
▼ Figure 6
Correct
Header unit
A
Follower unit
B
Follower unit
C
A view
Unit
[Vertical connection of branch units]
▼ Figure 7
Incorrect
To gas-side
To gas-side
branch unit
branch unit
14-EN
2/18/17 11:44 AM