Toshiba MMY-MAP0726FT6P-UL Installation Manual page 12

Table of Contents

Advertisement

Available languages

Available languages

(1) Outdoor unit connecting pipe
Outdoor unit capacity type (*1)
Balance pipe side
072 type, 096 type
120 type
144 type
168 type
(2) Connecting pipe between outdoor units
Total capacity code of the outdoor
Suction gas side
units at downstream side (*1) (*7)
336
Ø1-3/8"
360 or more
Ø1-5/8"
(3) Main pipe
Total capacity code of all
Suction gas side
outdoor units
072, 096
120
Ø1-1/8"
144
Ø1-1/8"
168, 192
Ø1-1/8"
216, 240
Ø1-3/8"
264, 288, 312, 336
Ø1-3/8"
360 or more
Ø1-5/8"
(4) Branching pipe
Total capacity code of indoor units
Suction gas side
at downstream side (*1) (*2) (*3) (*8)
Below 61
61 to below 115.5
115.5 to below 153.5
Ø1-1/8"
153.5 to below 191.5
Ø1-1/8"
191.5 to below 239
Ø1-3/8"
239 to below 334
Ø1-3/8"
334 or more
Ø1-5/8"
(5) Single port type FS unit and indoor unit connection pipe
Indoor unit capacity code
007 to 012 type
015 to 018 type
021 to 054 type
072 to 096 type
(6) Branching, Multi port type FS unit, Single port long piping type FS unit and indoor
unit connection pipe
Indoor unit capacity code
49 ft or less
Pipe length
007 to 012 type
(Actual length)
Over 49 ft
49 ft or less
Pipe length
015 to 018 type
(Actual length)
Over 49 ft
021 to 054 type
072 to 096 type
21-EN
1122001001-2_EN-FR.indb 11
1122001001-2_EN-FR.indb 11
Discharge
Suction gas side
gas side
Ø3/8"
Ø7/8"
Ø3/4"
Ø3/8"
Ø1-1/8"
Ø3/4"
Ø3/8"
Ø1-1/8"
Ø7/8"
Ø3/8"
Ø1-1/8"
Ø7/8"
Discharge
Liquid side
gas side
Ø1-1/8"
Ø7/8"
Ø1-1/8"
Ø7/8"
Discharge
Liquid side
gas side
Ø7/8"
Ø3/4"
Ø1/2"
Ø3/4"
Ø1/2"
Ø7/8"
Ø5/8"
Ø7/8"
Ø3/4"
Ø1-1/8"
Ø3/4"
Ø1-1/8"
Ø7/8"
Ø1-3/8"
Ø7/8"
Discharge
Liquid side
gas side
Ø5/8"
Ø1/2"
Ø3/8"
Ø7/8"
Ø3/4"
Ø1/2"
Ø7/8"
Ø5/8"
Ø7/8"
Ø3/4"
Ø1-1/8"
Ø3/4"
Ø1-1/8"
Ø7/8"
Ø1-3/8"
Ø7/8"
Gas side
Liquid side
Ø3/8"
Ø1/4"
Ø1/2"
Ø1/4"
Ø5/8"
Ø3/8"
Ø7/8"
Ø1/2"
Gas side
Liquid side
Ø3/8"
Ø1/4"
Ø1/2"
Ø3/8"
Ø1/2"
Ø1/4"
Ø5/8"
Ø3/8"
Ø5/8"
Ø3/8"
Ø7/8"
Ø1/2"
– 11 –
(7) Y-shaped branching joint (*3) (*4)
Total capacity code of indoor units
Liquid side
on downstream side from
Y-shaped branching joint (*4) (*5)
Ø1/2"
Below 61
Ø1/2"
Ø5/8"
61 to below 134.5
Ø3/4"
134.5 to below 239
239 or more
(8) Branching header
Total capacity code of the indoor units
on downstream side from
branching header (*4) (*5) (*6)
For 4 branching
For 8 branching
(9) Outdoor unit connection piping kit
Total capacity code of the outdoor
units at downstream side (*1) (*7)
Below 247
247 or more
(10) Flow Selector unit (*9)
Single port type (*10) / Single port long piping type (*11)
Total capacity code of outdoor units
on downstream side from FS unit
Below 38
38 to below 61
61 to 96 or less
Multi port type (*11) (*12)
Total capacity code of outdoor units
on downstream side from FS unit
Below 61
(*1) : The capacity code of outdoor unit and indoor unit, please refer to "Capacity code of indoor and outdoor units".
(*2) : If the size of the pipe to be selected is larger than the size of the main pipe, please use the same pipe size as the main pipe.
(*3) : Two pipes in downstream of FS unit and cooling only indoor unit use liquid pipe and suction gas pipe.
(*4) : The first branching joint, select at capacity code of outdoor unit.
(*5) : If the total capacity code of indoor units exceed the capacity code of outdoor unit, select the size from the capacity code of the outdoor unit.
(*6) : For one line pipe line of header branching, total 57 capacity code of indoor units is connectable.
If connecting the branching header to the first branch section with the capacity code of outdoor unit is more than 114 (kBtu/h) and less than
247 (kBtu/h), use the RBM-2043FUL (4 branch), and RBM-HT2083FUL (8 branch).
Also, the branching header cannot be used for the first branch section when the capacity code of outdoor unit is more than 247 (kBtu/h).
(*7) : The main pipe is the starting point. The follower unit side is the downstream side.
(*8) : Selection piping is the starting point. The indoor unit side is the downstream side.
(*9) : If the code of outdoor unit is over 408, "Flow Selector unit" is available for only Multi port type and Single port long piping type.
(*10): The group connection of the multiple indoor units is possible up to maximum 8 units, and it is possible only within one FS unit.
(*11): The group connection of the multiple indoor units is possible up to 8 units if one remote controller is used, and it is possible up to 7 units if two
remote controllers are used. The group connection of the multiple indoor units is possible only within one branch.
(*12): In the downstream of the multi type FS unit,the header branch cannot be used.
Model name
For 3 pipe
For 2 pipe
RBM-BY55FUL
RBM-BY55UL
RBM-BY105FUL
RBM-BY105UL
RBM-BY205FUL
RBM-BY205UL
RBM-BY305FUL
RBM-BY305UL
Model name
For 3 pipe
For 2 pipe
Below 134
RBM-HY1043FUL
RBM-HY1043UL
134 to below 240
RBM-HY2043FUL
RBM-HY2043UL
Below 134
RBM-HY1083FUL
RBM-HY1083UL
134 to below 240
RBM-HY2083FUL
RBM-HY2083UL
Model name
RBM-BT14FUL
RBM-BT24FUL
Model name
RBM-Y0383FUL / RBM-Y1124FUL
RBM-Y0613FUL / RBM-Y1804FUL
RBM-Y0963FUL / RBM-Y2804FUL
No. of branch
Model name
4
RBM-Y0611F4PUL
6
RBM-Y0611F6PUL