Wiring The Sdi-12 Serial Bus; Wiring The Rs-485 Bus - Infinite AERINOS ADS-260 User Manual

Table of Contents

Advertisement

3.7 Wiring the SDI-12 Serial Bus

SDI-12 is an asynchronous, ASCII, serial communications protocol that was
developed for intelligent sensory instruments that typically monitor environmental
data. The communication is achieved by digital communications. The addressing
system allows data recorder to communicate with several microprocessor-based
sensors over a single line.
ADS-200 is compliant to the SDI-12 Standard Version 1.2 and supports extended
commands for sensor configuration, in terminal mode. ADS-200 can collect data from
several SDI-12 sensors for a total amount of 8 measurement channels.
SDI-12 connections:
J6-2: SDI data line
J6-1: GND
J5-2: 12V excitation output. The 5V excitation output (J5-3) can be used instead, for
sensors with a 5VDC supply option.
It is recommended to read the sensor manufacturers' Sensor Manual and the SDI-12
Specification by the SDI-12 Support Group
functions of the ADS-260 device.

3.8 Wiring the RS-485 Bus

ADU-500 supports the popular MODBUS protocol over a differential RS-485 bus. The
bus line is internally terminated with a 120Ω resistor.
ADS-260 User Guide
[1]
before utilizing the corresponding
10