Automatic refrigerant amount detection function
This function detects amount of refrigerant in the system through refrigerant amount detection operation
Press the Tact switch "K2" 5
Satisfy the temperature condition
Check the amount of refrig er
Check stability
Yes
Connect S-Net Pro
Judge the amount of refrigerant
Judgment on the amount of
refrigerant: Normal /
Excessive /
Insufficient
❋ After refrigerant amount detection is finished, if you see "K9 Ed" on the display and cannot check the refrigerant amount
from the S-net pro and S-checker, it means insufficient degree of supercooling.
96
Start
times
ant
No
Judgment not
available
End
Input S-CHECKER signal
Satisfy the temperature condition
Check the amount of refrig er
Check stability
Yes
Judge the amount of refrigerant
Judgment on the amount of
refrigerant: Normal /
Excessive /
Insufficient
ant
No
Judgment not
available