Space requirement for installation
Module installation
Front side
Over 100 (4)
<Case 1>
Over 100 (4)
Over 100 (4) Over 100 (4)
Front side
Over 100 (4)
Over 100 (4) Over 100 (4)
Front side
❋ For <Case 1> or <Case 3>
Height of the wall on the front side should not be higher than 1500mm (60 inch).
Height of the wall on the air inlet side should not be higher than 500mm (20 inch).
Height of the wall on the side is not limited.
If the height of the wall exceeds by certain value (h1, h2), additional clearance [(h1)/2, (h2)/2 : Half of the exceeded
distance] should be added to the service space (S1, S2).
S1+h1/2
28
Over 100 (4)
Over 100 (4)
Over 100 (4)
Over 100 (4)
<Case 3>
Unit: mm (inch)
S2+h2/2
Over 300 (12)
Over 400
Over 400
Front
(16)
side
<Case 2>
Unit: mm (inch)
Height of
the wall is
unlimited
(16)