Samsung DVM S AM MXVAFC Series Installation Manual page 57

Table of Contents

Advertisement

Installing the distribution header
1. Select the reducer that fits the diameter of the pipe.
Pipe*
To outdoor unit
Socket
<Liquid side>
❋ Pipe : Separately purchased item
2. If the number of connected indoor unit is fewer than ports on the distribution header, block the unused ports with caps.
Welding part
Provided item
Connect in
order
<Liquid side>
For A~J type distribution header :
Connect the distribution header to the connection pipe with the provided reducer.
NOTE
For K~Z type distribution headers :
Cut the provided socket, according to the diameter of the connection pipe, before connecting it.
Connect the indoor units in order, while respecting the direction of the arrow shown in the illustration.
When indoor units are connected to same distribution head, indoor unit must be connected in order of their
CAUTION
capacity, from largest to smallest.
Provided item
Socket
Pipe*
Pipe*
To indoor unit
To outdoor unit
Case of blocking the unused
distribution header ports
To indoor unit
Socket
<Gas side>
Connect in
order
Case of blocking the unused
distribution header ports
<Gas side>
10mm~15mm (0.39~0.59 inch)
Socket
Pipe *
57

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvm s am mxvajc seriesDvm s am140mxvafc/azDvm s am220mxvajcDvm s am220mxvafcDvm s am080mxvafc/azDvm s am100mxvafc/az ... Show all

Table of Contents