Setting outdoor unit option switch and key function
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Silent mode
Main
High-head
Main
condition setting
Long-pipng
condition
setting (Setting
Main
is unnecessary
if high-head
condition is set)
Energy control
Operaton
Main
(B type PBA)
Main
Unused Option
Main
Channel address
Main
Snow
accumulation
Main
prevention control
84
0
0
0
1
0
2
0
3
0
7
0
4
0
5
0
6
0
0
0
1
0
8
0
2
0
3
0
0
0
1
0
9
0
2
0
0
0
1
1
0
0
2
1
1
0
0
1
2
0
0
A
U
1
3
0 ~ 15
0
0
1
4
0
1
Function of the option
Disabled (Factory default)
LEVEL 1 / Auto
LEVEL 2 / Auto
LEVEL 3 / Auto
LEVEL 4 / External contact
LEVEL 5 / External contact
LEVEL 6 / External contact
Disabled (Factory default)
Level 1 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
Level 2 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
Height difference type 2
(Outdoor unit is lower than
indoor unit)
Disabled (Factory default)
LEVEL 1
LEVEL 2
Basic (Factory default)
Energy saving
Power
Unused Option
Unused Option
Automatic setting (Factory
default)
Manual setting for channel
0~15
Enabled (Factory default)
Disabled
Remarks
Enables the silent mode for night-
time in cooling mode (It operates
automatically depending on the
temperature.)
However, if the external contact
interface module (MIM-B14) is
used, entering the silent mode is
available with contact signal.
When outdoor unit is located
40~80m above the indoor unit
When outdoor unit is located over
80m above the indoor unit
When indoor unit is over 30 m
above the outdoor unit
When equivalent length of
farthest indoor unit from
the outdoor unit is between
100~170m
When equivalent length of
farthest indoor unit from the
outdoor unit is over 170m
Energy control option of
designated operation sequence
❋ Operating in energy saving
mode, capacity might
decrease compared to normal
operation mode
Unused option by this model
Unused option by this model
Address for classifying the
product from upper level
controller (DMS, S-NET 3, etc.)
During snow accmulation , the fan
may spin even when the unit is
not in operation