Technical Details - Pilz PNOZ X7 Operating Manual

Table of Contents

Advertisement

PNOZ X7

Technical details

Order no. 774049 – 774054
See below for more order numbers
General
Approvals
Electrical data
Supply voltage
Voltage
Kind
Voltage tolerance
Output of external
power supply (AC)
Frequency range AC
Duty cycle
Inputs
Number
Voltage at
Input circuit DC
Start circuit DC
Feedback loop DC
Current at
Input circuit DC
Start circuit DC
Feedback loop DC
Max. overall line capacit-
ance Clmax
Relay outputs
Number of output con-
tacts
Safety contacts (N/O),
instantaneous
Max. short circuit current
IK
Utilisation category
In accordance with the
standard
Operating Manual PNOZ X7
19692-EN-06
774049
CCC, CE, EAC (Euras-
ian), KOSHA, TÜV, cU-
Lus Listed
774049
48 V
AC
-15 %/+10 %
2 VA
50 - 60 Hz
100 %
774049
1
48 V
24 V
24 V
45 mA
40 mA
40 mA
37 nF
774049
2
1 kA
EN 60947-4-1
774053
CCC, CE, EAC (Euras-
ian), KOSHA, TÜV, cU-
Lus Listed
774053
110 V
AC
-15 %/+10 %
2 VA
50 - 60 Hz
100 %
774053
1
110 V
24 V
24 V
14 mA
40 mA
40 mA
37 nF
774053
2
1 kA
EN 60947-4-1
774054
CCC, CE, EAC (Euras-
ian), KOSHA, TÜV, cU-
Lus Listed
774054
115 V
AC
-15 %/+10 %
2 VA
50 - 60 Hz
100 %
774054
1
115 V
24 V
24 V
17 mA
40 mA
40 mA
37 nF
774054
2
1 kA
EN 60947-4-1