Huawei FusionServer Pro 5885H V5 Technical White Paper page 61

Table of Contents

Advertisement

Huawei FusionServer Pro 5885H V5 Server
Technical White Paper
Category
Altitude
Corrosive gaseous
contaminant
Particle contaminant
Acoustic noise
Issue 09 (2020-06-05)
Specifications
● Operating altitude ≤ 3050 m (10006.44 ft)
– If the server complies with ASHRAE Class A2, the
maximum operating temperature decreases by
1°C (1.8°F) for every increase of 300 m (984.25
ft) in altitude above 900 m (2952.76 ft).
– If the server complies with ASHRAE Class A3, the
maximum operating temperature decreases by
1°C (1.8°F) for every increase of 175 m (574.15
ft) in altitude above 900 m (2952.76 ft).
– If the server complies with ASHRAE Class A4, the
maximum operating temperature decreases by
1°C (1.8°F) for every increase of 125 m (410.10
ft) in altitude above 900 m (2952.76 ft).
● HDDs cannot be used at an altitude of over 3000 m
(9842.4 ft).
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
● The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the
equipment room be monitored by a professional agency.
The declared A-weighted sound power levels (LWAd)
and declared average bystander position A-weighted
sound pressure levels (LpAm) listed are measured at
23°C (73.4°F) in accordance with ISO 7779 (ECMA 74)
and reported in accordance with ISO 9296 (ECMA 109).
● Idle:
– LWAd: 5.3 Bels
– LpAm: 40.1 dBA
● Operating:
– LWAd: 6.1 Bels
– LpAm: 50.4 dBA
NOTE
The noise generated during operation varies depending on the
server configuration, load, and ambient temperature.
Copyright © Huawei Technologies Co., Ltd.
6 Product Specifications
55