Application Range; Qualified Refrigerants And Oils; Application Limits And Operating Envelopes - Emerson Copeland Scroll Digital ZRD36KRE Application Manuallines

Compressors for comfort, precision and process cooling
Table of Contents

Advertisement

2.5

Application range

2.5.1 Qualified refrigerants and oils

IMPORTANT
It is essential that the glide of refrigerant blends (primarily R450A) be carefully
considered when adjusting pressure and superheat controls.
Oil recharge values can be taken from Copeland Scroll compressors brochures or Copeland™
brand products Select software at www.climate.emerson.com/en-gb.
Compressor
Qualified refrigerants
Copeland™ brand products
standard oil
Servicing oils
Table 3: Qualified refrigerants and oils

2.5.2 Application limits and operating envelopes

CAUTION
Inadequate lubrication! Compressor breakdown! The superheat at the
compressor suction inlet must always be sufficient to ensure that no refrigerant
droplets enter the compressor. For a typical evaporator-expansion valve
configuration a minimum stable superheat of at least 5K is required.
Application envelopes for the various refrigerants can be found in Select software, available at
www.climate.emerson.com/en-gb.
6
ZRD*KRE
R450A, R513A
Emkarate RL 32 3MAF
Emkarate RL 32 3MAF, Mobil EAL Arctic 22 CC
C6.2.44/0219/E