1) 115 VOLT CORD CONNECTION

This unit has been built, tested and approved with a cord connected 115VAC built in Ground Fault Circuit Interrupter
(GFCI).
The cord must only be plugged into a receptacle that is connected to a
dedicated 15A breaker or fuse.
DO NOT extend the connection by the use of an extension cord. This will
void the warranty and could cause damage to the spa and its' users.
GFCI Test Procedure:
1. With the GFCI plugged into a grounded 115VAC, 15A outlet press
the yellow TEST button.
2. The spa should shut off and a small light between the TEST and
RESET buttons should be lighted.
3. Press the red RESET button to reset the GFCI and start the spa.
FAMILIARIZE yourself with the test procedure for the GF CI. TEST the GFCI upon every use of the spa.
If the GFCI does not shut the spa off when the TEST button is pressed or does not start up when the RESET button is
pressed DO NOT USE THE SPA. Contact your dealer and/or a qualified electrician immediately. Take steps to ensure
that no person(s) can use the spa while the problem is being reviewed and corrected.
Note: In new installations, GFCI trippings due to mis-wiring are very common.
If the breaker is properly wired, GFCI trippings can occur when the total amount of current drawn by the spa exceeds
the rating of the breaker. Such an occurrence, however, is very unlikely, since each output of the spa pack is
individually fused and fuses will blow before the GFCI trips. A current leak to the ground will also make the GFCI trip. If
one or more of the components is faulty and there is a leak of more than 5 mA, the GFCI will trip to prevent
electrocution.

2) CORD AND PLUG CONNECTED

- CONVERTIBLE UNITS USING VS SERIES SPA PACK
This spa was factory made as a 120 VAC spa. Its' power input can be converted to a 240VAC permanent connection.
This must be done by employing a qualified electrician and in accordance with local electrical codes.
Note: This 240V conversion allows the heater to operate as 4Kw @ 240V. The jet pump, ozone and AV outputs
remain 120V.
Connect only to a circuit protected by a Class A Ground Fault Circuit Interrupter
14
DOC: OM-SUNRISE-19
CAUTION:
when converting to the permanent connection mode.
Sunrise Spas 2019 Owner's Manual