1. DESCRIPTION
Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems
utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-
3000P Valve comes complete as shown in Figure 8. The system piping is pressurized with air
or nitrogen to serve both as a means of supervising the integrity of the piping network and as
one portion of the system release operation. This feature serves to prevent undetected leaks
on the system piping network. If the system piping or a sprinkler is damaged, the supervisory
pressure is reduced and a "low air" supervisory alarm is activated.
This pilot operated externally reset valve also includes an internal check diaphragm
which eliminates the need for a separate check valve being installed in the system riser.
Double interlocked electric/pneumatic release preaction systems require the use of one 24
VDC normally closed (NC) electric solenoid and one pneumatic actuator. The electric sole-
noid is connected to a compatible release control panel and compatible detection devices.
The pneumatic actuator is controlled by the air pressure that is contained within the sprinkler
system piping. In fire conditions, both the solenoid and a sprinkler must open in order for the
G-3000P Valve to operate. When both the solenoid and pneumatic actuator open, the prim-
ing water is relieved from the internal prime chamber assembly. The prime chamber assem-
bly collapses, and water passes through the G-3000P Valve and internal check diaphragm to
the system piping network. The entire sprinkler system fills with water.
Double interlock electric/pneumatic release preaction systems are commonly used in cold
storage applications and other areas where it is important to control accidental water dis-
charge due to inadvertent damage to the sprinkler piping.
2. LISTING AND APPROVALS
cULus Listed: VLFT
FM Approved: Refrigerated Area Sprinkler Systems
3. TECHNICAL DATA
Specifications:
Pressure Rating: 250 PSI (17.2 bar) Water Working Pressure
Factory Hydrostatically Tested to: 500 PSI (34.5 bar)
Friction Loss (Given in feet of Schedule 40 pipe based on Hazen & Williams formula C = 120):
Model G-3000P Valve: 17.3'
12" Section of Pipe: 1'
Water Supply Control Valve: 10'
Model G-3000P Valve C v Factor: 225
Valve Color: Black
Material Specifications:
Refer to Figure 11.
Ordering Information:
Available since 2010.
Part Number: Double Interlock Electric/Pneumatic Preaction System Riser Assembly: 16191-1 (Refer to Figure 8)
Accessories:
(Refer to Figure 9.)
Drain Manifold: 16212
Model E-1 Accelerator: 08055
Model LD-1 Anti-Column Device: 14800
4. INSTALLATION:
A. General Installation Instructions
1. For proper operation and approval, the valve must be installed in the vertical position as trimmed from the factory. DO NOT
modify the factory assembled trim except as described in this technical data sheet.
2. A 12" section of pipe is provided with the G-3000P Double Interlock Electric/Pneumatic Preaction Riser Assembly. Prior to
valve maintenance, this section of pipe may be removed to provide clearance for lifting the cover from the body.
3. The G-3000P Valve must be installed in an area not subject to freezing temperatures or physical damage. If required, provide
Form No. F_011610
18.10.25
TECHNICAL DATA
P65
3" MODEL G-3000P
DOUBLE INTERLOCK PREACTION
WITH ELECTRIC/PNEUMATIC RELEASE
Q = C v
Q = Flow
C v = Flow Factor (GPM/1 PSI ∆P)
∆P = Pressure Loss through Valve
S = Specific Gravity of Fluid
Viking Technical Data may be found on
The Viking Corporation's Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Replaces Form No. F_011610 Rev January 6, 2012
Page 1 of 12
∆P
S
(Added P65 Warning.)

Advertisement

loading

Summary of Contents for Viking G-3000P

  • Page 1 3. The G-3000P Valve must be installed in an area not subject to freezing temperatures or physical damage. If required, provide Form No.
  • Page 2 3” MODEL G-3000P TECHNICAL DATA DOUBLE INTERLOCK PREACTION WITH ELECTRIC/PNEUMATIC RELEASE The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Figure 1 - Air Supply Options Form No. F_011610...
  • Page 3 Model G-3000P Valve and associated equipment. 4. The Viking E-1 Accelerator should be installed at the location indicated in Figure 1 when required. B. Air Supply Design 1. Air Compressor Size Viking recommends tank-mounted air compressors be supplied for double interlock electric/pneumatic release preaction systems.
  • Page 4: Field Adjustments

    2. Automatic air supplies must be regulated, restricted, and from a continuous source. A Viking Air Maintenance Device should be installed on each system equipped with a tank mounted compressor, plant air or nitrogen. For compressors with a capacity less than 5.5 ft...
  • Page 5 3” MODEL G-3000P TECHNICAL DATA DOUBLE INTERLOCK PREACTION WITH ELECTRIC/PNEUMATIC RELEASE The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Figure 5 - Trim Components 4. Open the flow test valve.
  • Page 6: Operation

    The closed pneumatic actuator, and the normally closed solenoid valve prevent prime water from escap- ing the prime chamber of the G-3000P Valve. When prime water enters the prime chamber, the rolling diaphragm is pressurized, causing it to expand downward onto the water seat.
  • Page 7 With both the pneumatic actuator and solenoid valve open, prime water is drained from the prime chamber, causing the G-3000P Valve to open, filling the sprinkler piping with water. Water from the intermediate chamber of the G-3000P Valve pressurizes the sensing end of the PORV, causing the PORV to open. The open PORV prevents water pressure from building in the prime chamber should the solenoid or pneumatic actuator close.
  • Page 8: Maintenance

    To Test Sprinkler System “Low Supervisory Air” Alarm: 1. To prevent operation of the G-3000P Valve and filling the system with water during the test, DO NOT operate the electric detection system during test. Consider closing the main water supply control valve.
  • Page 9 (4) toward the prime line and remove from the body. 2. Inspect and replace if necessary. 3. Inspect the seat. The seat should be clean and free of foreign material. If the seat is damaged, the G-3000P Valve must be replaced.
  • Page 10 3” MODEL G-3000P TECHNICAL DATA DOUBLE INTERLOCK PREACTION WITH ELECTRIC/PNEUMATIC RELEASE The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Part Number 16191-1: Model G-3000P Valve Model G-3000P Double Interlock,...
  • Page 11 3” MODEL G-3000P TECHNICAL DATA DOUBLE INTERLOCK PREACTION WITH ELECTRIC/PNEUMATIC RELEASE The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Figure 10 - Installation Dimensions Form No. F_011610 18.10.25...
  • Page 12 3” MODEL G-3000P TECHNICAL DATA DOUBLE INTERLOCK PREACTION WITH ELECTRIC/PNEUMATIC RELEASE The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Figure 11 - Model G-3000P Valve Components/Replacement Parts Item...