61-1007RK/61-0198RK Detector Operator’s Manual Part Number: 71-0200RK Revision: A Released: 4/12/11 www.rkiinstruments.com...
Page 2
Typical calibration frequencies for most applications are between 6 and 12 months, but can be required more often or less often based on your usage. 61-1007RK/61-0198RK Combustible Gas Detector...
Page 3
Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
± 5% of reading or ± 2% of full scale (whichever is greater) WARNING: When using the 61-1007RK, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 61-1007RK and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 61-1007RK as described in this manual.
61-1007RK-02 which has a detection range of 0 - 5,000 ppm, the 61-1007RK-03 which has a detection range of 0 - 5% volume, the 61-1007RK-05 which has a detection range of 0 - 50% volume, and the 61-1007RK-10 which has a detection range of 0 - 100% volume.
The junction box allows you to install the detector at a mounting site that is remote from a controller and it protects the detector wiring connections. Two 3/4” NPT conduit hubs allow you to mount the detector to the junction box and connect the wiring from the 61-1007RK/61-0198RK Combustible Gas Detector • 3...
Select a site that minimizes the possibility of someone breathing on the detector. The exhaled CO may cause an alarm. 3.10 3/4 NPT Female 3.65 6.80 Max Rubber Spacers J-Box IR CO2 Sensor 1 1/2-20 Thread for Calibration Cup Figure 3: Mounting the CO Detector 4 • 61-1007RK/61-0198RK Combustible Gas Detector...
NEMA 4X. Connect the wires to the terminals opposite the detector leads. CAUTION: Leave the shield drain wire insulated and disconnected at the 61-1007RK. You will connect the opposite end of the cable’s drain wire at the controller. Secure the junction box cover to the junction box.
Page 10
Detector to a Controller 10. If using shielded cable, connect the cable’s drain wire to an available chassis ground at the controller. RKI controllers typically have a ground stud that is a convenient grounding location. 6 • 61-1007RK/61-0198RK Combustible Gas Detector...
Remove the calibration cup from the detector. You may leave the sample tubing connected to the calibration cup for convenience. 10. Store the components of the calibration kit in a safe and convenient place. 61-1007RK/61-0198RK Combustible Gas Detector • 7...
Screw the regulator into the calibration cylinder. Turn the on/off knob on the regulator counterclockwise to open the regulator. Apply gas to the detector for one minute. Verify that the reading is within ± 20% of the gas concentration. 8 • 61-1007RK/61-0198RK Combustible Gas Detector...
5. If the fail condition continues, contact • The detector zero RKI for further instruction. signal is low enough to cause a fail condition. • The detector is malfunctioning. 61-1007RK/61-0198RK Combustible Gas Detector • 9...
Page 14
Turn off the controller. Turn off or unplug power to the controller. Unscrew the detector housing cap from the detector housing body. Make sure not to 10 • 61-1007RK/61-0198RK Combustible Gas Detector...
(see Figure 4 on page 6). See the controller operator’s manual and the controller’s detector head specification sheet for the 61-1007RK detector to verify the connections to the controller are correct.
Although there is no particular calibration frequency that is correct for all applications, a calibration frequency of every 6 months is adequate for most infrared CO detector applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 6 months for the infrared detector.
The 0-50 %volume and 0-100 %volume detectors will not display a reading in fresh air because their ranges are too large. Store the components of the calibration kit in a safe and convenient place. 61-1007RK/61-0198RK Combustible Gas Detector • 13...
Parts List Table 3 lists replacement parts and accessories for the 61-1007RK and 61-0198RK CO detectors. Table 3: Parts List Part Number Description 07-0039RK Detector housing cap gasket 18-0400RK-01 Junction box with spacers 33-0157RK Hydrophobic disk membrane for detector cap...