Summary of Contents for RKI 61-1007RK

  • Page 1 61-1007RK/61-0198RK Detector Operator’s Manual Part Number: 71-0200RK Revision: A Released: 4/12/11 www.rkiinstruments.com...
  • Page 2 Typical calibration frequencies for most applications are between 6 and 12 months, but can be required more often or less often based on your usage. 61-1007RK/61-0198RK Combustible Gas Detector...
  • Page 3 Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
  • Page 4: Table Of Contents

    Parts List ..............14 61-1007RK/61-0198RK Combustible Gas Detector...
  • Page 5: Overview

    ± 5% of reading or ± 2% of full scale (whichever is greater) WARNING: When using the 61-1007RK, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 61-1007RK and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 61-1007RK as described in this manual.
  • Page 6: Description

    61-1007RK-02 which has a detection range of 0 - 5,000 ppm, the 61-1007RK-03 which has a detection range of 0 - 5% volume, the 61-1007RK-05 which has a detection range of 0 - 50% volume, and the 61-1007RK-10 which has a detection range of 0 - 100% volume.
  • Page 7: Junction Box

    The junction box allows you to install the detector at a mounting site that is remote from a controller and it protects the detector wiring connections. Two 3/4” NPT conduit hubs allow you to mount the detector to the junction box and connect the wiring from the 61-1007RK/61-0198RK Combustible Gas Detector • 3...
  • Page 8: Installation

    Select a site that minimizes the possibility of someone breathing on the detector. The exhaled CO may cause an alarm. 3.10 3/4 NPT Female 3.65 6.80 Max Rubber Spacers J-Box IR CO2 Sensor 1 1/2-20 Thread for Calibration Cup Figure 3: Mounting the CO Detector 4 • 61-1007RK/61-0198RK Combustible Gas Detector...
  • Page 9: Wiring The Co 2 Detector To A Controller

    NEMA 4X. Connect the wires to the terminals opposite the detector leads. CAUTION: Leave the shield drain wire insulated and disconnected at the 61-1007RK. You will connect the opposite end of the cable’s drain wire at the controller. Secure the junction box cover to the junction box.
  • Page 10 Detector to a Controller 10. If using shielded cable, connect the cable’s drain wire to an available chassis ground at the controller. RKI controllers typically have a ground stud that is a convenient grounding location. 6 • 61-1007RK/61-0198RK Combustible Gas Detector...
  • Page 11: Startup

    Remove the calibration cup from the detector. You may leave the sample tubing connected to the calibration cup for convenience. 10. Store the components of the calibration kit in a safe and convenient place. 61-1007RK/61-0198RK Combustible Gas Detector • 7...
  • Page 12: Maintenance

    Screw the regulator into the calibration cylinder. Turn the on/off knob on the regulator counterclockwise to open the regulator. Apply gas to the detector for one minute. Verify that the reading is within ± 20% of the gas concentration. 8 • 61-1007RK/61-0198RK Combustible Gas Detector...
  • Page 13: Troubleshooting

    5. If the fail condition continues, contact • The detector zero RKI for further instruction. signal is low enough to cause a fail condition. • The detector is malfunctioning. 61-1007RK/61-0198RK Combustible Gas Detector • 9...
  • Page 14 Turn off the controller. Turn off or unplug power to the controller. Unscrew the detector housing cap from the detector housing body. Make sure not to 10 • 61-1007RK/61-0198RK Combustible Gas Detector...
  • Page 15: Replacing The Co 2 Detector

    (see Figure 4 on page 6). See the controller operator’s manual and the controller’s detector head specification sheet for the 61-1007RK detector to verify the connections to the controller are correct.
  • Page 16: Calibration Frequency

    Although there is no particular calibration frequency that is correct for all applications, a calibration frequency of every 6 months is adequate for most infrared CO detector applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 6 months for the infrared detector.
  • Page 17: Setting The Response Reading

    The 0-50 %volume and 0-100 %volume detectors will not display a reading in fresh air because their ranges are too large. Store the components of the calibration kit in a safe and convenient place. 61-1007RK/61-0198RK Combustible Gas Detector • 13...
  • Page 18: Parts List

    Parts List Table 3 lists replacement parts and accessories for the 61-1007RK and 61-0198RK CO detectors. Table 3: Parts List Part Number Description 07-0039RK Detector housing cap gasket 18-0400RK-01 Junction box with spacers 33-0157RK Hydrophobic disk membrane for detector cap...