Page 2
Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage. 35-3001-04 Carbon Monoxide Sample-Draw Detector GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
Page 3
Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
WARNING: When using the 35-3001-04, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 35-3001-04 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 35-3001-04 as described in this manual.
Page 8
The sensor flow control valve is mounted to the flowmeter circuit board above the flowmeter. The sensor flow control valve adjusts the flow rate to the sensor. Turn the valve’s knob 4 • 35-3001-04 Carbon Monoxide Sample-Draw Detector GlobalTestSupply www.
Page 9
A red wire and a blue wire extend from the CO amplifier and allow connection to the detector/amp terminal strip. 35-3001-04 Carbon Monoxide Sample-Draw Detector • 5 GlobalTestSupply www.
Page 10
The black test point (CAL 2) in the upper left corner is the negative (-) test point and the red test point (CAL 1) in the upper right corner is the positive (+) test point. 6 • 35-3001-04 Carbon Monoxide Sample-Draw Detector GlobalTestSupply www.
1/4” O.D. rigid polypropylene, Teflon, or flexible polyurethane tubing may be used. RKI Instruments, Inc. recommends using either 1/4” O.D. x 1/8” I.D. or 1/4” O.D. x 0.170” I.D. tubing based on your length requirements. See “Specifications” on page 1 for maximum tubing lengths based on tubing size.
Push 1/4” O.D. rigid polypropylene or rigid Teflon sample tubing into the fitting until it stops. Flexible polyurethane tubing may be used with an appropriate insert. RKI Instruments, Inc. recommends using either 1/4” O.D. x 1/8” I.D. or 1/4” O.D. x 0.170” I.D. tubing based on your length requirements.
Page 14
Figure 5: Wiring the Sample-Draw Detector to a Controller If shielded cable is used, connect the cable’s drain wire to an available chassis (earth) ground at the controller. RKI controllers typically have a ground stud that can be used to ground the cable’s drain wire.
Plug the voltmeter leads into the test points on the amplifier. Plug the positive lead into the red (+) test point; plug the negative lead into the black (-) test point. Verify a voltmeter reading of 100 mV (± 2 mV). 35-3001-04 Carbon Monoxide Sample-Draw Detector • 11 GlobalTestSupply www.
Preparing for the response test NOTE: This procedure describes the RKI calibration kit that includes a demand flow regulator. Verify that the display reading at the controller is 0 ppm. If the display reading is not 0 ppm, set the zero reading as described in “Calibration” on page 19, then continue this procedure.
Verify that the sensor wiring is correct and secure. “Wiring the Sample-Draw Detector to a Controller” on page 9 describes sensor wiring connections. Calibrate the sample-draw detector as described in “Calibration” on page 19. 35-3001-04 Carbon Monoxide Sample-Draw Detector • 13 GlobalTestSupply www.
If the fail condition continues, replace the sensor as described in “Replacing Components of the Sample-Draw Detector” on page 14. If the fail condition continues, contact RKI Instruments, Inc. for further instruction. Slow or No Response/Difficult or Unable to Calibrate Symptoms •...
Page 19
14. Calibrate the sample-draw detector as described in “Calibration” on page 19. Replacing the Charcoal Filter Turn off the controller. Turn off power to the controller. Open the housing door of the sample-draw detector. 35-3001-04 Carbon Monoxide Sample-Draw Detector • 15 GlobalTestSupply www. .com Find Quality Products Online at:...
Page 20
Install the new particle filter onto the tubing stub. Be sure the arrow on the particle filter is pointing toward the inlet line. Turn on power to the controller. Turn on the controller. 16 • 35-3001-04 Carbon Monoxide Sample-Draw Detector GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
Repeat steps 3 and 4 if necessary. Use the sensor flow control valve to set the flow to 1.0 SCFH. Make sure the sample-draw detector’s Fail LED is off. 35-3001-04 Carbon Monoxide Sample-Draw Detector • 17 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
Screw the inlet fitting tube nut back onto the fitting body. See “Connecting the Sample Lines to the Sample-Draw Detector” on page 8 for instructions to install a new piece of tubing into the fitting. 18 • 35-3001-04 Carbon Monoxide Sample-Draw Detector GlobalTestSupply www.
3 months is adequate for most carbon monoxide sample draw detector applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 3 months for the carbon monoxide sample draw detector.
Close the housing door. Follow the instructions in the controller’s operator’s manual to exit the calibration mode. Store the components of the calibration kit in a safe and convenient place. 20 • 35-3001-04 Carbon Monoxide Sample-Draw Detector GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...