65-2437RKSS-05 Carbon Monoxide Detector Operator’s Manual Part Number: 71-0439 Revision: P1 Released: 9/14/17 RKI Instruments, Inc. www.rkiinstruments.com...
Page 2
Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage. 65-2437RKSS-05 CO Detector...
Page 3
Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
WARNING: When using the 65-2437RKSS-05, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 65-2437RKSS-05 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 65-2437RKSS-05 as described in this manual.
Description This section describes the components of the 65-2437RKSS-05 CO detector. The 65-2437RKSS-05 consists of the 65-2438 CO detector and junction box. Terminal Block Black Locking Set Screw Stainless Steel J-Box CO Detector Figure 1: CO Detector Component Location 2 • 65-2437RKSS-05 CO Detector...
Page 7
The disc-shaped charcoal filter is secured to the face of the CO sensor with a rubber boot. The charcoal filter prevents interference gases (hydrogen sulfide [H S] and certain hydrocarbons) from producing false CO readings. 65-2437RKSS-05 CO Detector • 3...
• Select a site where the target gas is likely to be found first. NOTE: If your application does not require a specific mounting site, mount the detector at approximately breathing level. 4 • 65-2437RKSS-05 CO Detector...
Remove the junction box cover. WARNING: To maintain the explosion proof classification of the CO detector, a conduit seal must be used within 18 inches of the junction box conduit hub used for wiring to the controller. 65-2437RKSS-05 CO Detector • 5...
Page 10
Route the cable or wires leading from the CO detector through one of the conduit hubs at the controller housing. Use appropriate conduit fittings and construction technique for the environmental rating of the controller. RKI controllers are typically rated NEMA 4X.
If using shielded cable, connect the cable’s drain wire to an available chassis ground at the controller. RKI controllers typically have a ground stud that is a convenient grounding location. 10. Reinstall the junction box cover. Start Up This section describes procedures to start up the CO detector and place the detector into normal operation.
This procedure describes a test to verify that the CO detector responds properly to carbon monoxide. It describes a test using a fixed flow regulator with an on/off knob. RKI Instruments, Inc. recommends using a 0.5 LPM (liters per minute) fixed flow regulator.
Unexplained • Controller indicates a • Charcoal filter is 1. Replace charcoal filter. Upscale CO reading that saturated and no 2. If difficulties continue, contact RKI for cannot be verified. longer scrubbing out Readings or further instructions. interfering gases. Alarms •...
Carefully plug the replacement sensor into the four-socket pattern that is located in the detector housing. 10. Make sure the cap gasket is in place and screw the detector housing cap back onto the detector housing body. 10 • 65-2437RKSS-05 CO Detector...
Page 15
Although there is no particular calibration frequency that is correct for all applications, a calibration frequency of every 3 months is adequate for most CO detector applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 3 months for the CO detector.
It describes calibration using a calibration kit that includes a calibration cup, calibration gas, sample tubing, and a fixed flow regulator with an on/off knob. RKI Instruments, Inc. recommends using a 0.5 LPM (liters per minute) fixed flow regulator.
Page 17
NOTE: If you do not allow the gas reading to decrease below the alarm points, then unwanted alarms may occur. 10. Verify that the controller display reading decreases and stabilizes at 0 ppm CO. 11. Store the components of the calibration kit in a safe and convenient place. 65-2437RKSS-05 CO Detector • 13...