Power Supplies

DC Power Supply Connections

Connecting a DC Cable Harness to the Chassis Power Supply

When plugging in the cable, insert the connector end of the cable harness into the power supply connector
until it clicks firmly into place. This is an indication that the connector is secure and properly seated.

Connecting a DC Cable Harness to the DC Power Source

Safety Guidelines
Before connecting the DC cable to a power source, be sure to follow these important guidelines:
Connect to a reliably ground -48VDC Selv source.
The branch circuit overcurrent protection must be rated 15A.
Use 12AWG copper conductors.
A readily accessible disconnect device that is suitably approved and rated shall be incorporated in the
field wiring.
It must be installed in a restricted access location.
Primary Ground Information
The product has been designed to be installed in a Common Bonding Network (CBN). The pin of the
Green/Yellow ground lead in the three pin cable connector is connected to the ground connector on the DC
power supply, which is identified by a Grounding symbol. The Green/Yellow lead wire at the other end of
the cable must be connected to a proper earth ground point.
The rear chassis has two ground holes. To properly ground the equipment, connect a Panduit Corporation
UL listed Lug, (Part number LCD8-10A-L) to the two threaded holes located at the rear, insert two 10-32,
3/8" threaded pan head screws into these ground holes, and connect them to a proper earth ground point,
using protective earthing conductor wire and 8AWG copper conductors.
Connection Details
For DC power supply units, make the following power connections:
Connect the power supply using the supplied DC cable. The cable consists of three 12AWG wires (Green/
Yellow, Black, Red).
One end of the cable has a three pin connector in a plastic housing that is inserted into a three pin input
connector on the power supply. The other end of the cable is connected to a fuse panel or other source of
-48VDC power.
Observe proper polarity when connecting to a fuse panel. The cable wire leads must be connected as
follows:
Green/yellow - ground
Black - return
Red - -48VDC
Note. The battery return conductor is an Isolated DC Return (DC-1).