WARNING
!
Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
If venting is included with spacers, the vent system must be supported every 3'(0.9m) for both vertical and
horizontal runs. Use support ring assembly W010-0067 or equivalent non-combustible strapping to maintain
the minimum clearance to combustibles for both vertical and horizontal runs. Spacers are attached to the
inner pipe at predetermined intervals to maintain an even air gap to the outer pipe. This gap is required
for safe operation. A spacer is required at the start, middle, and end of each elbow to ensure this gap is
maintained. These spaces must not be removed.
This appliance uses a 5" (127mm) exhaust / 8" (203.2mm) air intake vent pipe system. Refer to the
This appliance uses a 5" (127mm) exhaust / 8" (203.2mm) air intake vent pipe system. Refer to the
section applicable to your installation.
section applicable to your installation.
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
minimum vertical vent length can create difficulty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement,
configurations, allow several minutes (5-15) for the flame to stabilize after ignition. Although not a requirement,
it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be
it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be
insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for
insulated with the insulation wrapped in a protective sleeve to minimize condensation.
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a
firestop, vent pipe shield or attic insulation shield when penetrating interior walls, floor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint
suitable for 400°F (200°C). Application and performance of paint is the consumer's responsibility. Spot testing is
The vent terminal may be painted with high temperature paint to match exterior colours. Use an outdoor paint
recommended.
suitable for 400°F (200°C). Application and performance of paint is the consumer's responsibility. Spot testing is
recommended. Appliance should be off.
note:
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the
note:
initial installation.
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
initial installation.
alternate constructions, such as a chimney as part of the vent system, is not permitted.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
alternate constructions, such as a chimney as part of the vent system, is not permitted.
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from
vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and
must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab,
All vent measurements start at the base of the air collar of the appliance.
follow the installation procedure provided with the venting components. A starter adaptor must be used with the
following vent systems and may be purchased from the corresponding supplier:
You may reduce the appliance from 5"/8" venting to 4"/7" venting for horizontal and vertical rise applications.
Vent
Starter Adapter Part
Reducing must be done right off of the appliance and a new firestop spacer (W010-3440) will be required.
Manufacturer
Number
Duravent
W175-0170
Amerivent
5DSC-N2
Direct Temp
5DT-AA
SuperSeal
5DNA
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using
a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake
vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance
fl ue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the
following termination kits: wall terminal kit GD422-1, GD422R-1, or 1/12 to 7/12 pitch roof terminal kit GD410,
8/12 to 12/12 roof terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration
below grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot (1.5m) vent
kit GD420 or the 10 foot (3.1m) vent kit GD430.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to
a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year
to verify that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components
must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of
vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections)

3.0 minimum venting requirements

minimum venting requirements
Supplier
Wolf Steel
American Metal
Selkirk
Metal-Fab
Website
www.duravent.com
www.americanmetalproducts.com
www.selkirkcorp.com
www.mtlfab.com
W415-1707 / 07.04.17
EN
13