Outdoor Fan Motor Control - Toshiba RAS-05J2KVG-EE Service Manual

Split type
Hide thumbs Also See for RAS-05J2KVG-EE:
Table of Contents

Advertisement

Item
3. Outdoor fan
The blowing air volume at the outdoor unit side is controlled.
motor control
Receiving the operation command from the controller of
indoor unit, the controller of outdoor unit controls fan speed.
* For the fan motor, a DC motor with non-stage variable
speed system is used. However, it is limited to 8 stages for
reasons of controlling.
Air conditioner ON
(Remote controller)
Indoor unit controller
1) Outdoor unit
operation command
(Outdoor fan control)
2) Fan speed ≥ 400
when the motor stopped.
NO
Fan motor ON
3) Fan lock
NO
4) Motor operates as shown in the table below.
RAS-05J2AVG-EE
RAS-07J2AVG-EE
RAS-10J2AVG-EE
Compressor speed
RAS-13J2AVG-EE
RAS-16J2AVG-EE
RAS-18J2AVG-EE
Fan tap
To ≥ 38°C
To ≥ 28°C
To ≥ 15°C
To
To ≥ 5.5°C
To ≥ 0°C
To ≥ 0°C
When To is abnormal
Outdoor fan speed (rpm)
Tap
RAS-05J2AVG-EE
RAS-07J2AVG-EE
f0
0 0 0 0
f1
300
f2
370
f3
390
f4
460
f5
500
f6
520
f7
620
f8
720
f9
750
fA
780
fB
780
fC
900
fD
900
fE
900
fF
900
Operation flow and applicable data, etc.
YES
OFF status of
fan motor continues.
YES
Air conditioner
~ 31.7
In cooling operation
32.4 ≤ Hz
20.4 ≥ Hz < 31.2
42.0 ≤ Hz
20.4 ≥ Hz < 42.0
60.6 ≤ Hz
Hz < 20.4
20.4 ≥ Hz < 60.6
75.0 ≤ Hz
20.4 ≥ Hz < 75.0
75.0 ≤ Hz
20.4 ≥ Hz < 75.0
30.6 ≤ Hz
Hz < 13.8
13.8 ≥ Hz < 30.6
MIN
MAX
MIN
MAX
MIN
f6
fB
f8
fE
fA
f5
fA
f7
fE
f9
f3
f7
f5
f9
f7
f2
f5
f4
f7
f6
f1
f3
f3
f5
f4
f1
f2
f2
f4
f3
OFF
fB
OFF
fE
f1
RPM
RAS-10J2AVG-EE
0
0
300
300
370
370
390
390
460
460
500
500
520
520
620
620
720
720
750
750
780
780
780
780
900
900
900
900
900
900
900
900
Alarm
OFF
display
RAS-05J2AVG-EE
RAS-07J2AVG-EE
RAS-10J2AVG-EE
Compressor speed
RAS-13J2AVG-EE
RAS-16J2AVG-EE
RAS-18J2AVG-EE
Fan tap
MAX
To ≥ 10°C
fE
To < 10°C
fE
To
To < 5°C
fB
To < -3°C
f9
When To is abnormal
f7
f5
fE
RAS-13J2AVG-EE
RAS-16J2AVG-EE
0
0
300
200
370
300
390
300
460
360
500
440
520
500
620
550
720
600
750
650
780
700
780
700
880
800
880
950
950
950
950
950
- 40 -
FILE NO. SVM-19004
Description
1) The operation command sent
from the remote controller is
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.
2) When strong wind blows at
outdoor side, the operation of air
conditioner continues with the
fan motor stopped.
3) Whether the fan is locked or not
is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.
4) According to each operation
mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.
In heating operation
20.4 ≥ Hz < 46.2
20.4 ≥ Hz < 59.4
Hz < 20.4
20.4 ≥ Hz < 78.0
20.4 ≥ Hz < 67.8
20.4 ≥ Hz < 75.0
Hz < 16.8
16.8 ≥ Hz < 48.6
MIN
MAX
MIN
MAX
MIN
f7
f8
f9
fB
fE
fE
fE
fE
fE
fE
RAS-18J2AVG-EE
0
300
300
300
360
450
500
550
600
650
700
700
800
850
950
950
46.2 ≤ Hz
59.4 ≤ Hz
78.0 ≤ Hz
67.8 ≤ Hz
75.0 ≤ Hz
48.6 ≤ Hz
MAX
f9
fE
fE
fE
fE