12. Protection Control
12.1 Restart Control (Time Delay Safety Control)
The compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
•
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
•
This phenomenon is to balance the pressure inside the refrigerant cycle.
•
12.2 30 Seconds Forced Operation
Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation
•
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a
•
full cycle and return back to the outdoor unit.
12.3 Total Running Current Control
When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
•
operation will be decreased.
If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
•
However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3
•
minutes.
Model
Operation Mode
Cooling / Dry (A)
Cooling / Dry (B)
The first 30 minutes of cooling operation, (A) will be applied.
•
12.4 IPM (Power Transistor) Prevention Control
Overheating Prevention Control
•
o
When the IPM temperature rises to 95°C, compressor operation will stop immediately.
o
Compressor operation restarts after 3 minutes the temperature decreases to 90°C.
DC Peak Current Control
•
o
When electric current to IPM exceeds set value of 18.5A, the compressor will stop operate. Then, operation
will restart after 3 minutes.
o
If the set value exceeds again more than 30 seconds after the compressor starts, the operation will restart
after 2 minutes.
o
If the set value exceeds again within 30 seconds after the compressor starts, the operation will restart after 1
minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off.
PS36***
X (A)
Y (A)
X (A)
20
25.95
19
25.95
38°C
Outdoor air temperature
PS12***
Y (A)
X (A)
6.8
15.0
10.4
6.2
15.0
9.5
(B)
37°C
(A)
32
56
PS18***
PS24***
Y (A)
X (A)
14.7
12.9
14.7
12.4
Y (A)
19.0
19.0