Toshiba rav-sm1103at-e Installation Manual page 9

Split type
Hide thumbs Also See for rav-sm1103at-e:
Table of Contents

Advertisement

• When using an air conditioner under low outside
temperature conditions (Outside temp: -5 °C or
lower) in COOL mode, prepare a duct or wind
shield so that it is not affected by the wind.
• When installing the unit in an area where
snowfalls may be heavy, take steps to prevent the
unit from being adversely affected by the fallen or
accumulated snow.
• Either make the foundation higher or install a
stand (which is high enough to ensure that the
unit will be above the fallen or accumulated
snow) and place the unit on it.
• Attach a snow shield (locally procured).
<Example>
Suction hood (Side)
Suction hood
Discharge hood
(Rear side)
Fin
Fin
Suction
Suction
Necessary Space for Installation
(Unit: mm)
Obstacle at rear side
Upper side is free
1.
Single unit installation
EN-15
2.
Obstacles on both right and left sides
150 or
300 or
more
more
3.
Serial installation of two or more units
150 or
300 or
300 or
more
more
more
The height of the obstacle should be lower than
Discharge
the height of the outdoor unit.
Obstacle also above unit
150 or
more
Obstacle in front
Above unit is free
1.
Single unit installation
2.
Serial installation of two or more units
The height of the
obstacle should be
lower than the height
of the outdoor unit.
Obstacle also at the above unit
300 or
more
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1.
Single unit installation
2.
Serial installation of two or more units
300 or
more
- 8 -
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit should be lower than the height of the outdoor unit.
Standard installation
1,000 or
1,000 or
more
more
Installation of Outdoor Unit
• Before installation, check the strength and
horizontalness of the base so that abnormal sounds
do not emanate.
• According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
• As shown in the figure below, install the foundation
and vibration-proof rubber pads to directly support the
bottom surface of the fixing leg that is in contact with
and underneath the bottom plate of the outdoor unit.
* When installing the foundation for an outdoor unit with
downward piping, consider the piping work.
300 or
more
300 or
1,500 or
2,000 or
200 or
more
more
more
more
150
600
150
430
Drain hole
Knockout
Drain nipple
mounting hole
hole
EN-16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm1403at-e

Table of Contents