Phenomenon
I cannot log in to Remote
Control Software from another
PC after the LAN is
disconnected.
The language does not switch
with the Remote Control
Software.
The schedule setting changes
have not been reflected.
I would like to use the
software with other
centralized controllers.
I would like to use the
software with other
centralized controllers.
I want to use multiple units in
combination.
The multi outdoor unit's option
board control does not work.
About communication
settings in [Service settings].
The Unit does turn ON/OFF
even though the operation
interlock signal/stop interlock
signal is input.
54
Question
Have you logged in with the same
user ID?
Have you accessed the software from
more than 8 PCs?
Did you assign the PC's IP address
using a DHCP server?
Does the login user for the Windows
being used have write permission for
the Remote Control Software storage
location?
Are you trying to change the schedule
settings on both the Remote Control
Software and the main unit?
Centralized controllers that can be
used together within the same TCC-
LINK.
Centralized controllers that can be
used together within the same TCC-
LINK.
Number of units that can be used in
combination in the same TCC-LINK.
Do you want to use the multi outdoor
unit's option board?
Do you want to use centralized
controllers in combination or use the
local remote control prohibition
settings?
Has the interlock signal been input
from the time of activation?
Confirmation items
You must log in again from a PC with the LAN disconnected and log
out normally.
Up to 8 PCs can be accessed at the same time. The software may
not operate correctly if you connect to more than 9 PCs.
This Unit judges whether it is accessed from the same PC using the
IP address.
If the PC address is changed partway through by the DHCP server,
you may not be able to log in again after LAN disconnection. Please
set the PC that accesses this Unit to a fixed IP or reboot the Unit and
erase the login information.
Please allow write permission below the folder where Remote
Control Software is saved (initial setting: C:\Program Files\TOSHIBA
Carrier Corporation).
Right-click on the TOSHIBA Carrier Corporation folder, select the
[Properties] - [Security] Name, click the "Edit" button and check
[Allow] for [Full control] under different settings.
To change the schedule settings, please set only one of either the
main unit or the Remote Control Software.
It is possible to use up to 8 units together with all centralized
controllers including this Unit.
Ask service personnel to use them in combination.
It is possible to use up to 8 units together with all centralized
controllers including this Unit.
To use them in combination, please set [Menu] - [Service settings] -
[Communication] as follows.
DS25-1... Please turn this setting ON when using centralized
controllers in combination.
It is possible to use up to 8 units together with all centralized
controllers including this Unit.
To use them in combination, please set [Menu] - [Service settings] -
[Communication] as follows.
DS25-1... Please turn this setting ON when using centralized
controllers in combination.
When the centralized controller is connected, the functions of the
outdoor unit's option board become ineffective. Only one of the
centralized controller and the outdoor unit's option board can be
used.
If you change the setting to unnecessary, the Unit may not work
properly. If it has been set, please return it to the initial value (only
DS25-2 ON).
The following settings should be used.
DS25-1... To use centralized controllers in combination, turn this
setting ON.
DS25-3... If you want to continue the local remote control prohibited
status after returning from a power failure, please turn this setting
ON.
Since the interlock signal confirms the state by detecting the rising
edge and falling edge, if the interlock signal is input from the time of
activation, interlock control will not be performed. Please set so that
the interlock signal turns OFF at the time of activation.