Omron H5S-B Manual page 2

Weekly time switch
Table of Contents

Advertisement

H5S
Characteristics
Accuracy of operating time
Setting error
Influence of voltage
Influence of temperature
Cyclic error
Memory protection
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Approved standards
Weight
Note: The total error including the repeat accuracy, setting error, variation due to voltage change, and variation due to temperature change is
0.01% 0.05 s max., 0.01% indicates an error in the time interval of a set time.
Operation
Operation method
Operation
Display
Number of circuits
Setting method
Min. setting unit
Min. set interval
Number of steps that can be set
Note: Normally, an ON/OFF operation is counted as two steps (i.e., ON + OFF operations), a cyclic operation as four steps, and a pulse
operation as 1 step.
As described on page 5, Ordinary T imer Operation , the above number of steps will be sufficient if the Timer is turned ON and OFF at
the same time, and the number of steps will not need to be as many as the number of days to be used.
2
0.01% 0.05 s max. (see note)
Monthly difference 15 s (at 25 C) ( 4 s/week, 1 min/4 months)
5 years min. (at 25 C)
100 MΩ min. (between current-carrying terminals and non-current-carrying metal parts,
between operation circuit and contact control output circuit, and between non-continuous
contacts)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and non-current-carrying
metal parts and between operation circuit and contact control circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
1,500 V (100 ns wide, for 1 µs, 1 ns rise time,
generated by noise simulator)
Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
2
Destruction: 294 m/s
(30G)
2
Malfunction: 98 m/s
(10G)
Operating: –10 C to 55 C
Operating: 35% to 85%
50,000 operations min. (15 A at 250 VAC, resistive load)
50,000 operations min. (1 HP at 250 VAC, motor load)
50,000 operations min. (10 A at 250 VAC, inductive load (cosφ = 0.7))
50,000 operations min. (100 W at 100 VAC, lamp load)
10,000 operations min. (300 W at 100 VAC, lamp load)
UL (File No. E52800), CSA (File No. LR22310, 10 A at 250 VAC (general use), 15 A at
125 VAC (resistive load))
Approx. 200 g
Digital quartz
1. Weekly operation (multiple-day operation possible)
2. Cyclic operation
3. Pulse-output operation (Pulse width can be set in units of 1 s from 1 to 59 s and in units of
1 min from 1 to 60 min.)
4. Day override operation (Operation for one day can be also executed on any other day.)
5. Forced ON/OFF Operation
6. Manual or automatic operation selectable on recovery from power failure.
Digital indication by LCD (character height: 10 mm)
1. Day, hrs (a.m., p.m.), minutes (0:00 to 11:59 a.m., 0:00 to 11:59 p.m.)
2. Digital display of operation schedule during operation
3. Timing chart display of operation schedule during operation
2 independent circuits
Key switch
1 min
1 min
24 (total of 2 circuits) (see note)
polarity, and 0 to 360 phase. Square noise
H5S

Advertisement

Table of Contents
loading

This manual is also suitable for:

H5s-fb

Table of Contents