Heat Meter; Transport And Storage; Installation - oventrop Multidis SF Operating Instructions Manual

Stainless steel distributor/collector
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 15
„Multidis SF"
- The ball valves 1406483 and
1406484 feature a red T-handle.
The red T-handle identifies the
supply pipe.
- The ball valves 1406583 and
1406584 feature a blue T-handle.
The blue T-handle identifies the
return pipe.
The length with installed ball valve is
obtained by adding the length of the
stainless steel distributor "Multidis
SF" (L) and the length of the ball
valve (L1).

4.2 Heat meter

Standard heat meters G1 and G¾ can be
installed.
The dimensions of the heat meter
can be obtained from the heat meter
manual.
5.

Transport and storage

Transport the stainless steel distributor/collec-
tor in its original packaging.
Store the stainless steel distributor/collector
under the following conditions:
Temperature
-20 °C to +60 °C
range
Relative air
Max. 95 %
humidity
Particles
Store dry and free from
dust
Mechanical
Protected from mechani-
influences
cal agitation
Radiation
Protected from UV rays
and direct sunlight
Chemical influ-
Do not store together
ences
with solvents, chemicals,
acids, fuels or similar
substances
140655280-V01.02.2020
Transport and storage
6.

Installation

The brackets allow for the fixing of the distribu-
tor/collector onto the wall or in the cabinet.
1. Mount the flow distributor (at the top) and
the return distributor (at the bottom) into
the sound-absorbing brackets.
2. Fix them onto the wall or in the cabinet.
The supply and return pipe can be
connected from either the left or right
hand side.
NOTICE
Risk of damage due to lubri-
cants!
Seals may be destroyed by greasing
agents or oil.
f Do not use any greasing agents or
oil for the installation.
f Flush any dirt particles or grease
or oil residues out of the pipework
before installing the product.
f Consider the latest technical status
(e.g. VDI 2035), when choosing the
operating fluid.
f Install a strainer in the supply pipe
to avoid contaminated operating
fluids (VDI 2035).
23