Honeywell SILENT KNIGHT RA-2000 Manual

Honeywell SILENT KNIGHT RA-2000 Manual

Remote annunciator

Advertisement

RA-2000 Remote Annunciator

Installation

The optional Model RA-2000 red remote annunciator, shown in
Figure 1, performs the same functions as the on-board
annunciator. Operation is identical. The RA-2000 can be surface
or flush mounted and is available in gray color as
RA-2000GRAY.
Figure 1: Model RA-2000 Remote Annunciator
RA-2000 installation involves the following steps:
1.
Make sure power is off at the panel.
2.
Mount the RA-2000 in the desired location (see Section

"Mounting the RA-2000" ).

3.
Connect the RA-2000 to the panel (see Figure 2).
4.
Use the dipswitches on the back of the RA-2000 to assign
an ID# to the RA-2000 (see Section 4.10.1 of Manual P/N
151430).
5.
The RA-2000 module must be added to the system through
programming. JumpStart Auto Programming will add the
module automatically (refer to Manual P/N 151430).

Wiring Connections

Wire the RA-2000 to the FACP as Shown in Figure 2.
Figure 2: SBUS Connections

Specifications

Parameter
Operating Voltage:
24 VDC
Standby:
25 mA
Current
Alarm:
50 mA
Operating Temperature: 0° to 49° C (32° to 120° F)
Flush
Overall: 12-1/4" W x 11.5" H x 7/8" D
Mount:
31.1 cm W x 29.2 cm H x 2.2 cm D
See "Flush Mounting" for back box
dimensions.
Dimensions:
Surface
Including trim ring:
Mount:
12-1/4" W x 11.5" H x 3" D
31.1 cm W x 29.2 cm H x 7.6 cm D
Mounting the RA-2000
This section of the manual describes mounting the remote
annunciator. The annunciator can be flush- or surface-mounted.

Flush Mounting

This section of the manual describes flush mounting.
Follow these steps to flush mount the RA-2000
1.
The back box dimensions are 9-3/8" w x 8-3/8" h. The
minimum depth 2". The back box can be mounted prior to
the complete installation of the RA-2000 using any of the
mounting holes shown in Figure 3.
Mounting Holes
Mounting Holes
Figure 3: Back Box Mounting Holes
2.
Remove knockout holes as needed for wires. See Figure 4
Value

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SILENT KNIGHT RA-2000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Honeywell SILENT KNIGHT RA-2000

  • Page 1 RA-2000 Remote Annunciator Specifications Installation Parameter Value The optional Model RA-2000 red remote annunciator, shown in Operating Voltage: 24 VDC Figure 1, performs the same functions as the on-board Standby: 25 mA annunciator. Operation is identical. The RA-2000 can be surface Current Alarm: 50 mA...
  • Page 2 Model RA-2000 Installation Instructions for backbox knockout locations box level insert the rest of the mounting screws. Key Shaped Wire Knockouts Mounting Hole Wire Knockouts Back Box Mounting Holes Wire Knockouts Figure 4: Back Box Knockout Locations Figure 6: Back Box Surface Mount Holes Wire the Annunciator board to the main control panel.

Table of Contents