WARNING: Blower access door switch opens 115-v
power to furnace control. No component operation can
occur. Caution must be taken when manually closing this
switch for service purposes. Failure to follow this warn-
ing could result in electrical shock, personal injury, or
death.
NOTE: If thermostat terminals are jumpered before blower ac-
cess door switch is closed, blower will run for 90 sec before
beginning a heating or cooling cycle.
17. If furnace is operating properly, REMOVE TAPE TO
RELEASE BLOWER ACCESS DOOR SWITCH, replace
blower access door.
C. Cleaning Heat Exchanger
The following steps should be performed by a qualified service
technician.
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, they should be replaced rather than trying to clean
them thoroughly due to their intricate design. A build-up of soot
and carbon indicates that a problem exists which needs to be
corrected, such as improper adjustment of manifold pressure,
insufficient or poor quality combustion air, incorrect size, or
damaged manifold orifice(s), improper gas, or a restricted heat
exchanger. Action must be taken to correct the problem.
If it becomes necessary to clean the heat exchanger because of dust
or corrosion, proceed as follows:
1. Turn gas and electrical power to furnace OFF.
2. Remove control and blower access doors.
3. Disconnect vent connector from furnace flue collar.
4. Disconnect internal vent pipe and enclosure on downflow
furnaces only.
a. Remove internal vent pipe enclosure cover.
b. Disconnect and remove short piece of vent pipe from
within furnace.
NOTE: Vent pipe is SCREWED and RTV sealed to relief box.
c. Remove vent pipe enclosure by removing screw in upper
back. Push bottom side backward to release tabs.
5. Remove 2 screws that secure relief box. (See Fig. 6 or 7.)
6. Disconnect wires to the following components. Mark wires
to aid in reconnection of:
a. Blocked vent safeguard switch.
b. Inducer motor.
c. Pressure switch.
d. Limit overtemperature switch(es).
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing electrode.
h. Flame rollout switch(es), if applicable.
7. Remove complete inducer assembly and relief box from
furnace.
8. Remove 8 screws that secure flue collector box to center
panel. Be careful not to damage collector box.
9. Remove burner assembly and cell inlet plates. IMPOR-
TANT: Replace screws in center panel and cells before
cleaning.
NOTE: Be careful when removing burner assembly to avoid
breaking igniter. See Fig. 8 for correct igniter location.
BURNER
Fig. 8—Position of Igniter to Burner
10. Using field-provided small wire brush, steel spring cable,
reversible electric drill, and vacuum cleaner, clean cells as
follows:
a. Assemble wire brush and steel spring cable.
(1.) Use 48 in. of 1/4-in. diameter high-grade steel
spring cable (commonly known as drain clean-out
or Roto-Rooter® cable).
(2.) Use 1/4-in. diameter wire brush (commonly known
as 25-caliber rifle cleaning brush).
NOTE: The materials needed in (1.) and (2.) can usually be
purchased at local hardware stores.
(3.) Insert twisted wire end of brush into end of spring
cable, and crimp tight with crimping tool or strike
with ball-peen hammer. TIGHTNESS IS VERY
IMPORTANT.
(4.) Remove metal screw fitting from wire brush to
allow insertion into cable.
b. Clean each heat exchanger cell.
(1.) Attach variable-speed, reversible drill to end of
spring cable (end opposite brush).
(2.) Insert brush end of cable into upper opening of cell
and slowly rotate with drill. DO NOT force cable.
Gradually insert at least 36 in. of cable into 2 upper
passes of cell. (See Fig. 9.)
(3.) Work cable in and out of cell 3 or 4 times to obtain
sufficient cleaning. DO NOT pull cable with great
force. Reverse drill and gradually work cable out.
(4.) Insert brush end of cable in lower opening of cell,
and proceed to clean 2 lower passes of cell in same
manner as 2 upper passes.
(5.) Repeat foregoing procedures until each cell in
furnace has been cleaned.
(6.) Using vacuum cleaner, remove residue from each
cell.
(7.) Using vacuum cleaner with soft brush attachment,
clean burner assembly.