OPTIONAL ELECTRIC HEAT DATA - ELA150
No.
Electric Heat
of
Size
Steps
10 kW
1
1
1
1
15 kW
1
1
1
1
25 kW
3
3
1
1
35 kW
3
3
1
1
Electric heater capacity only - does not include additional blower motor heat capacity.
1
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
2
3
Volts
kW
1
Input
Input
Output
208
7.5
25,600
220
8.4
28,700
230
9.2
31,400
240
10
34,100
440
8.4
28,700
460
9.2
31,400
480
10
34,100
550
8.4
28,700
575
9.2
31,400
600
10
34,100
208
11.3
38400
220
12.6
43,000
230
13.5
47,000
240
15
51,200
440
12.6
43,000
460
13.5
47,,000
480
15
51,200
550
12.6
43,000
575
13.5
47,000
600
15
51,200
2
208
18.8
64,100
220
21
71,700
2
230
23
78,300
240
25
85,300
440
21
71,700
460
23
78,300
480
25
85,300
550
21
71,700
575
23
78,300
600
25
85,300
2
208
25
85,300
220
28
95,500
2
230
30.6
104,400
240
33.3
113,700
440
28
95,500
460
30.6
104,400
480
33.3
113,700
550
28
95,500
575
30.6
104,400
600
33.3
113,700
Total Unit + Electric Heat
2
Minimum Circuit
Btuh
Ampacity
3 hp
40
44
21
17
53
59
29
23
79
89
44
35
100
114
57
45
Page 16
Total Unit + Electric Heat
Maximum Overcurrent
Protection
5 hp
3 hp
47
40
51
45
25
25
20
20
60
60
66
60
32
30
26
25
86
80
96
90
48
45
38
35
108
100
121
125
60
60
48
45
5 hp
50
60
25
20
60
70
35
30
90
100
50
40
110
125
60
50