Toshiba MMK-UP0271HP-E Installation Manual page 33

Hide thumbs Also See for MMK-UP0271HP-E:
Table of Contents

Advertisement

Wiring connection for fl ow selector unit
How to connect the wiring of fl ow selector unit
Connect the power supply wire and the communication wire supplied with the fl ow selector unit to the
indoor unit.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and the clamp base.
3. Insert the control wire fully into the control/wired remote controller terminal block and secure it tightly
with screws.
4. Connect the control wire connector of the fl ow selector unit to the lead with a connector to the left of
the control/wired remote controller terminal block.
5. Clamp the control wire and the control wire of the fl ow selector unit with the cord clamp.
6. Install the clamp base with a screw.
7. Insert the power supply wire fully into the terminal block and secure it tightly with screws.
Tightening torque: 1.2 N·m (0.12 kgf·m)
Secure the earth line with the earth screw.
8. Clamp the power supply wire with the cord clamp.
9. Insert the power supply wire fasten terminal of the fl ow selector unit into the power supply terminal.
Secure the earth line with the earth screw.
10. Clamp the power supply wire of the fl ow selector unit tight with the cord clamp.
11. Attach the terminal cover, the front panel and the air inlet grille to the indoor unit.
Control wire
from the
flow selector
Control wire
Confi rm that every wires are stored in the electric parts box without getting caught before attaching the
terminal cover.
Connector
Terminal
block for
control/wired
remote
controller
wiring
Cord clamp
Power supply wire
CAUTION
‒ 32 ‒
Installation Manual
Power supply
terminal block
Earth screw for
flow selector unit
Cord clamp
Power supply wire
of flow selector unit
32-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmk-up0301hp-eMmk-up0361hp-e