Installing the Fireplace
Step 1
Locating the Fireplace
The diagram below shows space and clearance requirements
for locating a fireplace within a room.
Clearance
Requirements
The top, back, and sides of
the fireplace are defined by
stand-offs.
The minimum clearance to a
perpendicular wall extending
past the face of the fireplace is
one inch (25 mm).
The back of the fireplace may
be recessed 19 1/4 inch
(48.9cm) into combustible
construction.
The distance from the unit to
combustible constructions is
to be measured from the unit
outer wrap surface to the com-
bustible construction, NOT
from the screw heads that
secure the unit together.
Glass Front
Floor
Back
Sides
Top
Ceiling**
* Using supplied non-combustible board on top of front face.
** The clearance to the ceiling is measured from the top of
the unit, excluding the standoffs and collar.
Installation du foyer
Étape 1
Emplacement du foyer
Le schéma ci-dessous indique les spécifications de
dégagement à respecter dans le choix de lemplacement
du foyer dans une pièce.
36
0
1/2
1/2
*4
50
* Avec la plaque non combustible fournie sur la façade.
** Le dégagement entre lappareil et le plafond se mesure à
partir du dessus de lappareil, à lexclusion des entretoises
et du collet.
12
Spécifications de
dégagement
Le dégagement au-dessus, à
larrière et sur les côtés du
foyer est défini par des
entretoises.
Le dégagement minimal en-
tre le foyer et un mur perpen-
diculaire dépassant la façade
du foyer est de 25 mm.
Larrière du foyer peut être
encastré de 48,9 cm dans une
structure combustible.
La distance entre lappareil et
toute structure combustible
doit être mesurée de la
surface de la paroi extérieure
de lappareil à la structure
combustible, et NON PAS
depuis les têtes de vis qui
assemblent les différentes
parties de lappareil.
914
Porte en verre
0
Plancher
13
Arrière
13
Côtés
*102
Dessus
1270
Plafond**