Page 1
CONTROLLER ecoMAX360P1-C FOR PELLET FUEL BOILERS ecoSTER TOUCH* eSTER_x40* ecoSTER200* eSTER_x80* ecoNET300* ecoNET.apk ecoNET.app www.econet24.com functions available additional module B * devices are not the standard equipment of the controller. INSTALLATION AND OPERATING MANUAL ISSUE: 1.1_EN 11-2020...
Page 2
ELECTRIC DEVICE UNDER VOLTAGE! Before any action related to the power supply (cables connection, device installation etc.) check if the controller is not connected to the mains! Installation should be done by a person with appropriate electrical qualifications. Improper cables connection could result in the controller damage.
TABLE OF CONTENTS 12.9 ......29 PTICAL SENSOR CONNECTION 12.10 M .... 29 IXERS ROOM TEMPERATURE CONNECTION RECOMMENDATIONS REGARDING SAFETY ..4 12.11 C ......29 ONNECTION OF RESERVE BOILER GENERAL INFORMATION ........5 12.12 C ....... 30 ONNECTION OF ALARM SIGNALING 12.13 M ...........
dusts or liquids can cause fire or Recommendations regarding safety explosion. Thus, the controller should be separated from flammable dusts Requirements concerning safety and gases, e.g. by means of an described in detail in individual chapters of appropriate body. this manual. Apart from them, the following requirements should particular...
Applied symbols General information In this manual the following graphic symbols The controller ecoMAX360P1-C is a device are used: designed to control the operation of a boiler - useful information and tips, with automatic feeding of solid fuel with a igniter.
HUW settings* User menu - structure Preset HUW temp. HUW pump mode • Main menu Off, Priority, No priority Information HUW cont. hysteresis Boiler settings HUW disinfection HUW settings* Mixer 1-2 settings* Night time decrease Night time decrease Boiler, HUW container, Mixer, Circulation Summer/Winter pump* •...
4. functions having influence preset The controller support boiler temperature: following describes shortened manual of the controller. preset boiler temperature decrease thermostat Description controller disconnection, support controller operated pressing preset boiler temperature buttons that allow to select items from the decrease activated time...
expansion module B, the mixer information The parameter value Preset boiler temp., is windows are activated. by controller bypassed when the preset boiler temperature is controlled by weather sensor. Regardless of that, the preset boiler temp. is automatically increased to load the hot user water tank and power heating circuits of mixers.
The Cycle time OPERAT. parameter is located in the menu: Service settings → Burner settings → Operation Feeder operation time calculated automatically depending on the required current power of the burner, Feed efficiency and Calorific value of the fuel. Parameters of blow-in output for different power levels of the burner are available in the menu: Boiler settings →...
further increase in temperature. Burner’s 8.11 GRATE power in SUPERVISION mode and other Some boilers have an additional grate to parameters of Supervision are grouped in the burn other fuels such as wood waste, etc. To menu: activate the grid, move the parameters Service settings →...
• set simultaneous operation of CH and Once a week at night, in Monday at 2 a.m. pump with parameter the controller increases temperature of HUW priority. container. After 10minutes of keeping the silo at 70ºC the HUW pump is deactivated 8.14 HUW preset temperature settings and the silo returns to its normal operation.
In this configuration a thermostat can be factor the bigger correction of preset boiler connected. It will level inaccuracy of heating temperature factor. When set on value “0” curve adjustement in case when its value will preset mixer temperature is not corrected. be too big.
indicated by the symbol on the main screen. To activate time intervals, set the parameter Night time decrease for the given heating circuit to ON. The parameter Reduction value set the temperature reduction, one for all time intervals. Night time decreases can be defined separately for every day of the week set Schedule.
Service settings → CH and HUW settings Boiler settings → Fuel level → Fuel level Settings of time control of circular pump are calibration → Fuel level 100% analogical to settings of night reductions. In In main window the indicator will be set on defined time periods...
Manual control screen view: OFF – the device is turned off, ON – the device is turned on. ecoNET.app (iOS) Attention: long lasting activating of fan, feeder or other device may cause danger. 8.27 Cooperation with the room thermostat and room panel The controller can cooperate with: •...
transport, the device cannot be exposed to 10 Technical data vibrations greater than those typical of normal road transport. Power supply by controller 230V~, 50Hz Current consumed by 0,06 12 The Controller installation controller Maximum rated current 5 (5) A 12.1 Environmental conditions Controller protection rating IP 20...
After installation make sure that the device is Connection of the 230 VAC mains properly mounted and it is impossible to voltage to terminals 12-25 or to transmission terminal G1 results detach it from the mounting surface. controller damage Opening of the boiler door or flue poses a threat of electrocution.
Page 25
The controller terminals box: Connecting cables to the controller: 1 - cable clamps, 2 - cable clamp screws, 3 - voltage cables (mains 230 VAC), 4 - safe voltage cables (signal, below 15 VDC), 5 - mains cable connector 230 VAC, 6 - signal wires connector, 7 - protective wires connector.
12.5 Electric scheme Scheme of electrical connections: L, N, PE – mains power 230 VAC, PE – protective clamp, GR – earthing, CPU – controlling, FU – fuse (T6,3 A, 230 VAC), STB – connection to limiter of safety temperature (disconnects the fan and feeder), W – fan, PG – feeder, PHD – HUW pump, PB –...
Page 27
Scheme of electrical connections of the additional B module: T1 - mixer 1 temperature sensor type CT4, T2 – mixer 2 temperature sensor type CT4, T3 – upper buffer temperature sensor type CT4, T4 – lower buffer temperature sensor type CT4, RT1, RT2 – standard mixer 1 and 2 room thermostat type NO-NC, RELAY –...
controller cooperates only with 12.6 Connection of temperature sensors weather sensor of the CT4-P or CT6-P type. controller cooperates only with The use of other types of temp. sensors is temperature sensors of the CT4 type. The prohibited. use of other types of temp. sensors is The sensor should be installed on the coolest prohibited.
12.8 Temperature sensors checking controller or the sensor itself, but Temperature sensors can be checked by the burner flame detection will be incorrect. measuring their resistance given temperature. In case of big differences 12.10 Mixers room temperature between measured resistance value and connection values in table below, the sensor should be Room thermostat, connected to module B,...
Service settings → Output H (mod B) and then set the parameter Temp. reserve boiler activation on value different than zero, in the menu: Service settings → Boiler settings → Reserve boiler Deactivating control over additional boiler is done after setting zero value of switching off for this parameter.
circuit is maximal (in controller it is position 100% ON) and value position when temperature of mixer circuit is minimal (in controller it is position 0% OFF). Remember the position in order to later verification of proper connection. • Disconnect the electrical power to the controller.
button can be pressed only after the boiler Wireless radio connection of the eSTER_x40 water temperature drops. room thermostat or eSTER_x80 room panel requires connection to the ISM_xSMART radio module controller, in accordance with point 12.5 pairing between thermostat / panel and the radio module. A description of the pairing and operation of the wireless panel / thermostat can be found in the manuals of these devices.
b) Two-wire connection. Due to the increased power consumption, connecting the ecoTOUCH room panel, an external 5...12 VDC power supply with a current of min. 500 mA (max. 1,2 A), which is not standard equipment of the controller. Two-wire connection of the executive module with the room panel.
• Flush period Sup. 13 Service menu – structure Min. airflow output Fuel detection time Entering service menu requires Max. burner temp. entering the password. Boiler settings Service settings Thermostat select. Burner settings Min. boiler temp. Boiler settings Max. boiler temp. CH and HUW settings Boiler cooling temperature Buffer settings*...
14 Description of service parameters 14.1 Burner Parameter Description Firing-up Time to check whether the burner is already firing up. Only fan is operating. If the • Ignition test time flame has sufficient brightness, it switches to the OERATION mode without the BURNING OFF mode.
Interval between blows in the supervision in grate mode. The value should not be too • Flush period Sup. high so as not to cause excessive water heating in the boiler. Minimum airflow fan power which can be chosen by the user. It is only used to limit the Min.
Parameter determines how high the boiler temperature will be increased to load HUW tank, buffer and mixer cycle. Temperature increase is only realizing when it is Boiler inc. by HUW and Mixer necessary. When preset boiler temperature is at sufficient level then controller will not change it due to the fact of feeding the HUW tank, buffer or mixer cycle.
parameter in the range of 2..6. The greater the value of this parameter, the slower is the actuator reaction for temperature deviation. Setting too lower values can lead to unnecessary actuator Integr. time const. movements, too high value extending the time needed to find set value of the temperature.
The sensor is to be checked and replaced if 15 Alarms descriptions necessary. Alarm numbers displayed on the eSTER_x40 alarm deleted alarm wireless room thermostat. confirmation or activating and deactivating Boiler max. temp. exceeding power to the controller. Burner max. temp. exceeding Checking the temperature sensor is Boiler temp.
delay the process of freezing water, however in case of very low temperatures or by lack In order to take out the fuse, raise the fuse of electrical power it may not protect the holder using flat-blade screwdriver and take installation against freezing.
18 Possible faults description Symptoms Tips There are no signs of operation of device despite connection to Check if line fuses are not blown, replace if necessary. the network. Check: ▪ If in this time the HUW tank is not loaded and if preset temperature is set above the Preset boiler temperature on the display is different from the preset boiler temperature.
Need help?
Do you have a question about the eSTER_x40 Series and is the answer not in the manual?
Questions and answers