LG ACAH020HETB Installation And Owner's Manual page 18

Air-cooled cooling only inverter scroll chiller
Table of Contents

Advertisement

PLACEMENT CONSIDERATIONS
Clearance Requirements
Follow the ventilation (suction and discharge air flow) and service requirements as shown below and on the next page when choosing a
chiller installation area.
Ventilation Clearance Requirements
Air-cooled chillers must be installed in an open space or must have appropriate ventilation. If the chiller must be installed near one wall or under a
ceiling, there must be enough space for ventilation.
Installing Near One Wall
• If one side of the chiller is near a wall, and the height of the wall is
less than 32 inches, the clearance space between the chiller and
the wall must be a minimum of 32 inches.
• If one side of the chiller is near a wall, and the height of the wall
is greater than 32 inches, the clearance space between the chiller
and the wall must be a minimum of 32 inches plus half of h1 (differ-
ence between 32 inches and the total wall height).
Figure 8: Ventilation Clearance Requirements When Installing the Chiller
Along One Wall.
Wall
h
1
Min. 32+h /2
1
Concrete Slab or Base Materials
Minimum height of spring isolation should be at least 4 inches, or use a larger spring isolation that follows applicable local, NEC, or other codes.
18
Air
Min. 4 (Spring Isolation)
(Unit: Inches)
Installing Under a Ceiling
• If the chiller is installed under a ceiling, the clearance space
between the top of the chiller and the ceiling must be a minimum of
197 inches.
• If the front or back of the chiller is near a wall, the clearance space
between the chiller and the wall must be a minimum of 32 inches.
Figure 9: Ventilation Clearance Requirements When Installing the Chiller
Under a Ceiling.
Air
Min. 4 (Spring
Isolation)
Concrete Slab or Base Materials
Ceiling
Wall
Min. 32
(Unit: Inches)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents