Bryant 569J Installation, Start-Up And Service Instructions Manual page 23

Air-cooled condensing units 60 hz, with puron (r-410a) refrigerant sizes 07-14
Hide thumbs Also See for 569J:
Table of Contents

Advertisement

UNIT
V--- Ph--- Hz
208/230---3---60
460--- 3--- 60
569J*12D/E
575--- 3--- 60
208/230---3---60
460--- 3--- 60
569J*14D/E
575--- 3--- 60
UNIT
V--- Ph--- Hz
208/230---3---60
460--- 3--- 60
569J*12D/E
575--- 3--- 60
208/230---3---60
460--- 3--- 60
569J*14D/E
575--- 3--- 60
NOTE: See "Legend and Notes for Tables 10 and 11" below
Legend and Notes for Tables 10 and 11
LEGEND:
FLA
---
Full Load Amps
LRA
---
Locked Rotor Amps
MOCP ---
Maximum Over Current
Protection
NEC
---
National Electrical Code
RLA
---
Rated Load Amps
}
Units are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the listed
limits.
NOTES:
1. The MCA and Fuse values are calculated in accordance with
The NEC. Article 440.
2. Motor RLA and LRA values are established in accordance
with Underwriters' Laboratories (UL). Standard 1995.
3. The 575--- v units are UL, Canada--- listed only.
4. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to de-
termine the percentage of voltage imbalance.
Table 11 – Electrical Data — 569J*12- - 14D/E 60 Hz Units
WTIHOUT POWERED CONVENIENCE OUTLET
VOLTAGE
COMPRESSOR
RANGE
}
MIN
MAX
RLA
187
253
16
414
506
7.8
518
633
5.7
187
253
22.4
414
506
10.6
518
633
7.7
WTIH POWERED CONVENIENCE OUTLET
VOLTAGE
COMPRESSOR
RANGE
}
MIN
MAX
RLA
187
253
16
414
506
7.8
518
633
5.7
187
253
22.4
414
506
10.6
518
633
7.7
COMPRESSOR
1
2
LRA
RLA
LRA
WATTS
110
16
110
52
7.8
52
39
5.7
39
149
22.4
149
75
10.6
75
54
7.7
54
COMPRESSOR
1
2
LRA
RLA
LRA
WATTS
110
16
110
52
7.8
52
39
5.7
39
149
22.4
149
75
10.6
75
54
7.7
54
Example: Supply voltage is 230-3-60
% Voltage Imbalance
= 100 x
AB = 224 v
BC = 231 v
AC = 226 v
(224 + 231 + 226)
Average Voltage =
=
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
23
POWER
OFM (ea)
SUPPLY
FLA
MCA
MOCP
325
1.5
40.6
60
325
0.8
22.5
40
325
0.6
16.4
30
325
1.5
53.4
60
325
0.8
25.4
30
325
0.6
18.5
25
POWER
OFM (ea)
SUPPLY
FLA
MCA
MOCP
325
1.5
43.8
50
325
0.8
21.3
25
325
0.6
15.7
20
325
1.5
58.2
80
325
0.8
27.7
35
325
0.6
20.2
25
max voltage deviation from average voltage
average voltage
=
3
227
4
= 100 x
227
= 1.76%
681