unit disconnect switch or HACR switch is open. Other
connection methods will result in the convenience outlet
circuit being de-energized when the unit disconnect or
HACR switch is open. See Fig. 13.
UNIT
CONNECT
VOLTAGE
AS
CONNECTIONS
208,
L1: RED + YEL
230
240
L2: BLU + GRA
L1: RED
Splice BLU +
460
480
YEL
L2: GRA
L1: RED
575
600
L2: GRA
Fig. 13 - - Powered Convenience Outlet Wiring
The unit-powered convenience outlet has a 1000 VA rated
transformer. Maximum continuous current must not
exceed 8 Amps.
NOTICE
Convenience Outlet Utilization
Maximum Continuous use : 8 Amps 24/7
Fig. 14 - - Convenience Outlet Utilization Notice Label
Test the GFCI receptacle by pressing the TEST button on
the face of the receptacle to trip and open the receptacle.
Check for proper grounding wires and power line phasing
if the GFCI receptacle does not trip as required. Press the
RESET button to clear the tripped condition.
Fuse on power type: The factory fuse is a Bussman
"Fusetron" T-15, non-renewable screw-in (Edison base)
type plug fuse.
C10206
PRIMARY
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H1
H2 + H3
H4
H1
H2
50HJ542739
B
C10207
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Using unit-mounted convenience outlets: Units with
unit-mounded convenience outlet circuits will often
require that two disconnects be opened to de-energize
all power to the unit. Treat all units as electrically
energized until the convenience outlet power is also
checked and de-energization is confirmed. Observe
National Electrical Code Article 210, Branch Circuits,
for use of convenience outlets.
Installing Weatherproof Cover: A weatherproof while in
use cover for the factory installed convenience outlets is
now required by UL standards. This cover cannot be
factory mounted due its depth; it must be installed at unit
installation. For shipment, the convenience outlet is
covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit's control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECT
ALL
CONVENIENCE OUTLET.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/
in (13 mm) under screw heads are
2- -
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not overtighten).
Mount the weatherproof cover to the backing plate as
shown in Fig. 15. Remove two slot fillers in the bottom of
the cover to permit service tool cords to exit the cover.
Check for full closing and latching.
Fig. 15 - - Weatherproof Cover Installation
19
POWER
TO
UNIT
AND
C09022