This manual is valid for the bifacial double glass module types Avertissement CS3W-PB-AG, CS3W-MB-AG, CS3Y-MB-AG, CS3Y-PB-AG, Toutes les instructions devront être lues et CS6W-MB-AG, CS7N-MB-AG, CS7L-MB-AG, and mono- comprises avant de procéder à l’installation, facial double glass module types CS6R-H-AG, CS6RA-H-AG, le câblage, l’exploitation et/ou l’entretien des panneaux.
connector. The copper ribbons used in our solar modules to interconnect solar cells use a thin solder coating layer that Do not allow children or unauthorized contains lead (CAS no. 7439-92-1). persons near the installation site or module storage area. Under normal or reasonably foreseeable conditions of use, exposure to the lead that is contained in our solar ...
Table 1: Low temperature correction factors for open- Impp = the highest 3-hour current average resulting α circuit voltage from the simulated local simultaneous irradiances on the front and rear sides of the PV array accounting for Correction Factor Lowest Expected elevation and orientation.
pallets touching the top of the cabinet door. For 6W- 12 modules and frames should be aligned with one MB-AG, the thickness of forklift teeth should be less another on the pile. than 75mm and the length of the forklift teeth should Do not place excessive loads on the module or twist the ...
Page 7
Prior to installing modules, please obtain information accessories required to maintain a specific System Fire about any requirements and necessary approvals for Class Rating should be clearly specified in the the site, installation and inspection from the relevant installation instructions and UL 2703 certification of the authorities.
Page 8
frame is connected to the bracket or where the Only modules with similar electrical parameters should grounding is connected. Should the installation location be connected in the same string to avoid or minimize be near the ocean, Canadian solar recommends mismatch effects in arrays.
CS3W/CS3Y/CS6W/CS7L/CS7N Cable length per lead = 1400 mm CS6R Cable length per lead = 1100 CS6RA Cable length per lead = 950 CS3W-PB-AG, CS3W-MB-AG, CS3Y-PB-AG, Note: Adjacent modules in the same row need to be rotated 180 degrees for proper CS3Y-MB-AG, installation.
Page 10
CS7N Cable length = 460 mm (+), 340 mm (-) & 2150 mm jumper cable CS6R Cable length = 410 mm (+), 290 mm (-) & 1500 mm jumper cable CS6RA Cable length = 410 mm (+), 290 mm (-) & 1100 mm jumper cable CS3W-PB-AG, CS3W-MB-AG, CS3Y-MB-AG,...
| 11 CORRECT CONNECTION OF CONNECTORS damage by taking appropriate precautions (e.g. placing them inside a metallic raceway like EMT conduit). Avoid Make sure that all connections are safe and properly exposure to direct sunlight. mated. The PV connector should not be subject to stress from the exterior.
| 12 The grounding method described below recommended for Canadian Solar. GROUNDING METHOD: BOLT + TOOTHED NUT + CUP WASHER. To fix the wire between the Then tighten the bolt flat washer and cup washer, using the toothed nut. place washer (concave side up) between...
| 13 Clamp material should be anodized aluminum alloy or check that the racking supplier specified bolt length steel of appropriate grade. comply with above requirement and will not affect installation. Clamp positions are of crucial importance for the reliability of the installation, the clamp centerline must ...
Page 14
| 14 Table 3: Approved bolting methods Inner four holes installation Middle four holes installation Outer four holes installation method A method A method A Inner four holes installation Middle four holes installation Outer four holes installation method B method B method B Installation Inner four...
| 15 6.2 MOUNTING METHODS: CLAMPING Pa is required. b) 40 mm (1.57 in) when uplift load ≤ 2400 Pa is The mechanical load test with these mounting methods required. were performed according to IEC 61215. 6. Ensure the clamp thickness is at least 3 mm (0.12 in). ...
Page 16
| 16 6.2.1 Clamp mounting on long side of frame and rails perpendicularly to the long side frame Max Mechanical Load (Pa) Module Types +3600/-2400 +5400/-2400 +5400/-3600 A Range (mm) CS3W 410-490 CS3Y 300-600 400-550 CS6R 400-550 450-500 CS6RA 300-450 350-400 CS6W 300-600...
Page 17
| 17 6.2.3 Clamp mounting on long side of frame and rails parallel to the long side frame. Max Mechanical Load (Pa) Module Types +3600/-2400 +3800/-3200 +4000/-3200 +4400/-3200 +4400/-3600 A1 Range (mm) CS3W 410-490 CS3Y 400-550 CS6W 400-500 CS6RA 300-400 CS7N/CS7L/CS6R 400-500 6.2.4 Four clamps on short side of frame and rails parallel to the long side frame.
| 19 1. Do not bend the module frame. 6.3 INSERTION SYSTEMS 2. Do not touch the front glass or cast shadow onto it. This mounting method has been certified by VDE and 3. Do not damage the surface of the frame. CSA, or qualified by Canadian Solar.
| 22 7.0 MAINTENANCE loose connections. The voltage and current present in an array during Do not make modifications to any component of the PV daylight hours are sufficient to cause a lethal electrical module (diode, junction box, connectors or others). shock.
Page 23
| 23 Dirt must never be scraped or rubbed away when dry, as this will cause micro-scratches on the glass surface. OPERATION PREPARATION Noticeable dirt must be rubbed away by gentle cleaning implement (soft cloth, sponge or brush with soft bristles).
| 24 ANNEX A: MECHANICAL AND ELECTRICAL RATINGS Standard Test Conditions are: Irradiance of 1000 W/m ±3% for Pmax, and ±5% for Isc & Voc. Specifications are AM1.5 spectrum, and cell temperature of 25°C. The subject to change without notice. tolerance of electrical characteristics is respectively within Table A: Mechanical and electrical ratings under STC Max.
Page 25
| 25 Max. Open Short Maximum Operating Operating Series Circuit Circuit Overall Dimension Weight power voltage current Fuse Model Type Voltage Current <mm> <Kg> Rating Pmax <W> Vmp <V> Imp <A> Voc <V> Isc <A> <A> CS3Y-490MB-AG 44.6 11.00 53.3 11.67 CS3Y-430PB-AG 41.6...
Page 26
| 26 Max. Open Short Maximum Operating Operating Series Circuit Circuit Overall Dimension Weight power voltage current Fuse Model Type Voltage Current <mm> <Kg> Rating Pmax <W> Vmp <V> Imp <A> Voc <V> Isc <A> <A> CS7L-585MB-AG 34.3 17.06 40.7 18.32 CS7L-590MB-AG 34.5...
| 27 ANNEX B: GUIDANCE ON MODULE TEMPERATURE FOR SEVERAL LOCATIONS The operational temperature of a PV module changes The operational module temperature is influenced by during the day and also from day to day throughout the the environmental temperature but also by how the year.
| 28 AMENDED EDITIONS AND DATES ·Rev 1.2 is released in June, 2019. ·Rev 1.21 is released in July, 2019. ·Rev 1.3 is released in September, 2019. ·Rev 1.4 is released in December, 2019. ·Rev 1.4 is released in December, 2019. ·Rev 1.5 is released in April, 2020.