User's
Manual
Models
UD310, UD320, UD350
Manual Setters
IM 05F01F12-41E
IM 05F01F12-41E
2004.6 3rd Edition

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Green Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for YOKOGAWA Green Series

  • Page 1 User’s Models Manual UD310, UD320, UD350 Manual Setters IM 05F01F12-41E IM 05F01F12-41E 2004.6 3rd Edition...
  • Page 2 Note: This user’s manual (IM 05F01F12-41E) is a re-edited, A4-size version of the IM 05F01F12-01E user’s manual that is supplied along with the product shipped. Therefore, both manuals have the same contents, except for some minor differences in the cross- referenced page numbers.
  • Page 3: Table Of Contents

    Please read through this user’s manual to ensure correct usage of the manual setter and keep it handy for quick reference. CONTENTS 1. Notice ..........................2 2. What is on the Front Panel? ..................3 3. Installing the Manual Setter ..................4 4.
  • Page 4: Notice

    Also, Yokogawa Electric Corporation assumes no liability to any party for any loss or damage, direct or indirect, caused by the use or any unpredictable defect of the instrument.
  • Page 5: What Is On The Front Panel

    WHAT IS ON THE FRONT PANEL? UD310 UD320 UD350 UD310 UD350 UD320 Monitoring Parts Name Function PV display (red) Indicates PV (measured value) and character information such as parameter codes and error codes. PV goes out when the setup parameter ”PVD” is set to OFF. SP display (green) Indicates SP (target setpoint) and character information such as parameter setpoints.
  • Page 6: Installing The Manual Setter

    INSTALLING THE MANUAL SETTER To prevent electric shock, the source of power to the manual setter must be turned off when mounting the manual setter on to a panel. To install the manual setter, select a location where: 1. No-one may accidentally touch the terminals; 6.
  • Page 7: Panel Cutout Dimensions And External Dimensions

    PANEL CUTOUT DIMENSIONS AND EXTERNAL DIMENSIONS Splash-proof construction is not available when the side-by-side close mounting method shown in the following figures, is chosen for any of the manual setters. 1. General Mounting min. 70 UD310 Unit: mm +0.6 2. Side-by-side Close Mounting ×...
  • Page 8: Wiring

    WIRING 1) Before you start wiring, turn off the power source and use a tester to check that the manual setter and cables are not receiving any power in order to prevent electric shock. 2) For safety, be sure to install a circuit breaker switch (of 5A and 100V AC or 220V AC, and that conforms to IEC60947) near the instrument so as to be operated easily, and clearly indicate that the device is used to de-energize the instrument.
  • Page 9 Cable Specifications and Recommended Products Power supply and relay contact output 600V vinyl insulated wire/cable, JIS C3307, 0.9 to 2.0mm Thermocouple input Shielded compensating lead wire, JIS C1610 RTD input Shielded wire (3-wire), UL2482 (Hitachi cable) Other signals Shielded wire Recommended Terminals Use M3.5 screw-compatible crimp-on terminals with an insulating sleeve, as shown below.
  • Page 10 Universal input-selectable Model UD310-00 Terminal Arrangement Measured Value (PV) Input input type RTD Input TC Input DC mV or V Input Alarm Outputs ALM2 NOTE ALM1 – – Do not use unassigned terminals as relay terminals. Receiving 4-20 mA DC Current Signals with the Manual Setter PV Retransmission Output When receiving 4-20 mA DC current signals,...
  • Page 11: Hardware Specifications

    HARDWARE SPECIFICATIONS Measured Value (PV) Input Alarm Functions Power Supply and Isolation • Power Supply Input: 1 point Alarm Functions • Input type: Universal; can be selected by software • Alarm types: 22 types Rated at 100-240VAC (±10%) • Input accuracy (at 23 ±2°C ambient temperature) AC/DC 24V, 20 to 29V of (waiting action can be set by software): Voltage...
  • Page 12: Key Operations

    KEY OPERATIONS To prevent electric shock, the manual setter should be mounted on the panel so as not to accidentally touch the terminals when power is being applied. (1)You can move between parameter setting displays using the key. (2)To change the parameter setpoint, ( i ) Change the display value with the key (the period flashes).
  • Page 13 The manual setter is shipped with the parameters set at the factory-set defaults. Check the default values against the “Parameter Lists” in the page 13 and 14, and change the parameter setpoints that need to be changed. This section explains how to set and register parameter setpoints. The procedure for changing Target Setpoint(SP) and Alarm 1 Setpoint(A1) can be found on "Changing Target Setpoint(SP)"...
  • Page 14 Power ON NOTE At first When measured input range code has been already set, the operating display shown below appears. is displayed Operating Display UD310 Measured input When “In” appears, press the Set the parameters value(PV) No display key to display the measured input as follows not to display a measured range code you want to use, then...
  • Page 15 Parameter Lists (1) Operating Parameters : Parameters changed rather frequently during operation. Code Name Setting range and unit Default User setting PV alarm Unit: °C/°F Alarm 1 Depends on the setpoint Setting range: [minimum value - (maximum value - alarm 1 type. minimum value)] to maximum value of measured input range (scale) Deviation alarm Unit: °C/°F...
  • Page 16 (2) Setup Parameters : Parameters rarely changed in normal use after once having been set. Code Name Setting range and unit Default User setting 1 to 23, 31 to 48 (See input range code list.) OFF, or the input Measured OFF: No input range code input type...
  • Page 17 Description of Measured Input Example of Temperature Input Example of Voltage Input °C °C -270 1370 (input signal) Minimum value Maximum value Measured Input Range of measured of measured Measured Input Range input range input range Measured Input Scale Display Scale °C °C -270...
  • Page 18 Description of Alarm hysteresis The alarms are output as relay outputs. Since a relay has a limited service life, excessive on/off actions will shorten the life of the relay. To prevent this, you can set a hysteresis for both alarm 1 and alarm 2 to moderate excessive on/off actions.
  • Page 19: Troubleshooting

    TROUBLESHOOTING In the event of an abnormality, perform the following checks as outlined by the flowchart. Is the manual setter defective? Completely inactive? Key operation failure? Display failure? I/O signal failure? Check the terminal connection Check key-lock Turn the power off, Verify the I/O spec.
  • Page 20 Blank Page IM 05F01F12-41E...
  • Page 22 Sales Branch Offices / Houten (The Netherlands), Wien (Austria), Zaventem (Belgium), Ratingen (Germany), Madrid (Spain), Bratislava (Slovakia), Runcorn (United Kingdom), Milano (Italy), Velizy villacoublay(France), Johannesburg(Republic of South Africa) YOKOGAWA AMERICA DO SUL S.A. Headquarters & Plant Praca Acapulco, 31-Santo Amaro, Sao Paulo/SP, BRAZIL CEP-04675-190 Phone: +55-11-5681-2400 Facsimile: +55-11-5681-4434 YOKOGAWA ENGINEERING ASIA PTE.