Celco Spider67 System Manual page 40

I/o module
Hide thumbs Also See for Spider67:
Table of Contents

Advertisement

 Analog value within unipolar current input/output range:
System Value
Decimalism
118.5149% 32767
27649
100%
27648
75%
20736
0.003617% 1
0%
0
-1
-75%
-20736
-100%
-27648
-27649
-118.519%
-32768
 Analog value within unipolar voltage input/output range:
System Value
Decimalism
118.5149% 32767
27649
100%
27648
75%
20736
0.003617% 1
0%
0
-1
-75%
-20736
-100%
-27648
-27649
-118.519%
-32768
Spider67 Profinet– Extensible industrial fieldbus I/O System
Input/Output Range
hexadecimal
0~20mA
7FFF
≥ 23.7 mA
6C01
6C00
20 mA
5100
15 mA
1
0
0 mA
FFFF
AF00
0 mA
9400
93FF
8000
0 mA
Input/Output Range
hexadecimal
0~5 V
7FFF
≥ 5.926 V
6C01
6C00
5 V
5100
3.75 V
1
0
0 V
FFFF
AF00
0 V
9400
93FF
8000
0 V
4~20mA
≥ 22.96 mA
Overflow, lock
the maximum
Overshoot
range
20 mA
16 mA
Rated range
4 mA
0 mA
Underflow, lock
the least value
0 mA
0~10 V
≥ 11.85 V
Overflow, lock
the maximum
Overshoot
range
10 V
7.5 V
Rated range
0 V
0 V
Underflow, lock
the least value
0 V
40 / 62

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sppn-gw-001

Table of Contents