Bryant 764A Installation, Start-Up And Service Instructions Manual page 6

Packaged air conditioners
Table of Contents

Advertisement

UNIT 564A AND 764A
OPERATING WEIGHT (lb)
COMPRESSOR TYPE
REFRIGERANT
Charge (lb)
REFRIGERANT METERING DEVICE
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
CONDENSER-FAN MOTOR
Cfm
Nominal Rpm
Motor Hp
Diameter (in.)
EVAPORATOR COIL
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR-FAN MOTOR
Blower Motor Size (in.)
Nominal Cfm
Rpm Range
Number of Speeds
Factory Speed Setting
Motor Hp
CONNECTING DUCT SIZES
Supply Air (in.)
Return Air (in.)
FIELD-SUPPLIED RETURN AIR FILTER†
Throwaway (in.)
*460-v motors are 2-speed only.
†Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute)
rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high capacity type.
Recommended filters are 1-in. thick.
CONDENSATE DRAIN HOLE
Fig. 7 — Condensate Connection Details
Fig. 8A — Condensate Trap (Using Tubing)
Table 1 — Physical Data
024
030
222
236
2.8
3.9
Copper Tubes, Aluminum Plate Fins
1...17
1...17
6.7
7.9
1600
2000
825
1100
1
1
8
4
20
20
Copper Tubes, Aluminum Plate Fins
2...15
3...15
2.8
2.8
10 x 8
10 x 8
800
1000
550-1000
550-1000
3
3
Low
Med
1
1
4
4
24 x 24
24 x 24
If the installation requires draining the condensate water
away from the unit, install a field-supplied 2-in. trap using
3
-in. OD tubing or piping to ensure proper drainage. See
4
Fig. 8A and 8B. Make sure that the outlet of the trap is at
least one in. lower than the unit drain pan condensate con-
nection to prevent the pan from overflowing. Connect a drain
tube using a minimum of
copper pipe (all field-supplied). Do not undersize the tube. Pitch
the drain tube downward at a slope of at least 1 inch in every
10 ft of horizontal run. Be sure to check the drain tube for
leaks. Prime trap at the beginning of cooling season start-up.
Allowable glues for condensate trap connection are: Stand-
ard ABS, CPVC, or PVC cement.
B. Field-Duct Connections
NOTE: The design and installation of the duct system must
be in accordance with the standards of NFPA for the instal-
lation of nonresidence-type air conditioning and ventilating
systems, NFPA 90A or residence-type, NFPA 90B, and/or
local codes and ordinances.
Units have duct flanges on the supply- and return-air open-
ings on the side of the unit. See Fig. 2-4 for connection sizes
and locations.
—6—
036
042
250
297
Reciprocating
R-22
4.7
4.4
Acutrol™ System
2...17
1...17
6.2
11.1
Propeller
2000
2600
1100
1100
1
1
4
4
20
20
3...15
3...15
3.1
3.9
Direct Drive
10 x 8
10 x 9
1200
1400
800-1050
800-1050
3
3
Low
Med
1
1
2
2
Round
14
14
24 x 24
24 x 24
Fig. 8B — Condensate Trap (Using PVC Piping)
-in. PVC,
3
4
048
060
310
350
6.1
7.5
2...17
2...17
8.6
10.7
2600
2800
1100
1100
1
1
4
4
20
20
3...15
4...15
4.3
4.9
10 x 9
10 x 10
1600
2000
1000-1100
950-1100
2
3*
Low
Low
1
3
4
Square
13.9 x 13.9
13.9 x 27.8
24 x 30
24 x 30
-in. CPVC, or
-in.
3
3
4
4

Advertisement

Table of Contents
loading

This manual is also suitable for:

564a

Table of Contents

Save PDF