Final checks

Block the flame sensor and turn off the remote controls: the
burner must start and then stop in lockout after approximately
5 s after ignition.
Free the flame sensor and turn off the remote controls: the
burner must stop in lockout.
Block the flame sensor when the burner is operating: the
flame must turn off and the burner stop in lockout within 1 s.
Turn on the remote control TL followed by TS while the
burner is operating: the burner must stop.
20166434
Start-up, calibration and operation of the burner
Make sure that the mechanical locking systems
on the adjustment devices are fully tightened.