1234 = password, 0 = zero, space counts as a character and is therefore important. Do not fill in password if
PIN is disabled on SIM-card
1234 N0 88888888 yyyy
Define the unit
ID-TEXT
phone number,
change password, if
(N0 = N + zero)
necessary and add
ID text
Receivers
1234 N1 11111111
Add
1234 N2 11111111 *
1234 N1
Delete
Text on input
1234 A0 BREAK TEXT
Add
1234 L0 END TEXT
1234 A0
Delete
1234 L0
1234 CT
Only alarm if text
is added
1234 V1 S yyyy zzzz
Add analog input 1
1234 V1 M 5 30
Add 2: Alarm
points
1234 V1 A LOW TEMP
Add text in LOW
interval
1234 V1 L NORMAL TEMP Alarm text in MEDIUM interval (between 5 and
Add text in
MEDÌUM interval
QUICK GUIDE for 6 modules
Set-up with text message
www.profort.com
1234 = current password, N0, 88888888=mobile
number of the unit.
Alternately yyyy=new four-digit password.
Alternately ID-text: First text in all messages from
the unit (max. 32 characters).
Adds receiver 11111111 in space no. 1 to receive
alarm as text message.
Adds receiver 11111111 in space no. 2 to receive
alarm as telephone call with tones.
Additional spaces (25 total):
N2..N9, NA (10), NB (11) .. NP (25),.
Deletes receiver in space no. 1
TEXT on input 0 by open/break. (A0..A3)
TEXT on input 0 by close/make. (L0..L3)
Deletes TEXT for input 0 by open/break.
(A0..A3)
Deletes TEXT for input 0 by close/make. (L0..L3)
The unit ignores input that has no text attached.
Set-up of the scale (yyyy = zzzz)
0-10 V (DIP-switch 1=ON) 0 10
0-20 mA. (DIP-switch 2=ON) 0 20
4-20 mA. (DIP-switch 2=ON) -5 20
PT100. (DIP-switch 3=ON) -309 115
Profort PTC. (DIP-switch 4=ON) -132 63
The unit sends alarm e.g. when temperature
passes 5 and 30 degrees C.
Alarm text in LOW interval (below 5 degrees
C.)
30 degrees C.)
Pg.