INSTALLING ACP LONWORKS
14
Before configuring the ACP Lonworks environment
The network environment of the ACP Lonworks can be set by the LCD and the buttons at the
front side of the ACP Lonworks.
The current ACP Lonworks information and the menu are displayed on the LCD, and the menu
can be changed and selected by pressing
▶) buttons.
Turning on the ACP Lonworks
Turn on the ACP Lonworks to set the network environment of the ACP Lonworks.
When the power switch is turned on, the ACP Lonworks booting screen is displayed on the LCD
as shown at the following figure, and
when booting is completed, the initial
ACP Lonworks screen is displayed.
!
NOTE
Software version
The software version of the current ACP Lonworks is displayed at the
initial ACP Lonworks screen.
Also, the software version may be different according to the manu-
facturing date of the ACP Lonworks.
Entering into the environment setup mode
Press 'SET' button of the ACP Lonworks to enter into the environment
setup mode of the ACP Lonworks. When the [SET] button is pressed for
the first time, the menu to set the IP address is displayed as shown below.
Press up/down(▲, ▼) button to place the arrow on the desired function.
• When you select [Network Info] and press [SET] button, it enters the No. 1 menu in the follow-
ing figure. In [Network Info] menu, input the network information such as IP address of the
ACP Lonworks.
• When you select [Function] and press [SET] button, it enters the No. 2 menu in the following
figure. In [Function] menu, ACP Lonworks software service function is
supported.
• In [LON GW Info] menu, you can
set the module type of the ACP
Lonworks as connected product.
!
CAUTION
• [Function] menu is used by the system air conditioner service
technician, so user shall never use this function.
• If this function is incorrectly used, it may cause disorder of the
ACP Lonworks.
and
PLNWKB000
LON
SVC
Wait for booting....
ACP Lonworks
SW ver. 1.0.0
I P 192.168.001.100
GW 192.168.001.001
button and Up/Down/Left/Right (▲, ▼, ◀,
PLNWKB000
[
S
E
] T
[
S
>
Function
LON GW Info
[
]
[
ACP Lonworks
SW ver. 1.0.0
I P 192.168.001.100
GW 192.168.001.001
ACP Lonworks
SW ver. 1.0.0
I P 192.168.001.100
GW 192.168.001.001
>
Function
LON GW Info
1
[Network Info]
IP
000.000.000.000
GW
000.000.000.000
MS
000.000.000.000
E
] T
MC
000000:00:00:00
DHCP no
2
[Function]
[S/W update]
]
[DB back up]
[DB recover]
[Data Logging]
[Language]
[Net Test]
3
[Set LON MODULE]
MODULE SELECT: 0
AC=>0 / AHU=>1 /
CHILLER=>2