Connecting ACP Lonworks and PC
It is the case of installing AC Manager in a
separate PC and connecting ACP Lonworks
and PC directly.
In such case, Ethernet cable shall be con-
nected as a cross cable.
Use Ethernet cable (cross cable) to connect to
LAN port of the ACP Lonworks.
ON
OFF
ON
OFF
!
CAUTION
Ethernet cable types
• You must distinguish if the Ethernet
cable to connect is a direct cable or a
cross cable.
• Also, connect after checking the exis-
tence of problem in the cable using LAN
tester.
Connecting LON communication
cable(TP/FT-10) of ACP Lonworks.
LON communication cable(TP/FT-10) should
be connected LON port of ACP Lonworks.
ACP Lonworks can connect with BMS
through LON communication cable(TP/FT-10).
There is non-polarity in TP/FT-10 communica-
tion cable conection.
Connect two line communication cable with
BMS.
Connection
with hub
Direct cable
Direct connection
with PC
Cross cable
Setting the ACP Lonworks
network address
After connecting the ACP Lonworks to various
devices via the cable, the network environ-
ment of the ACP Lonworks should be set by
driving the ACP Lonworks.
The following information should be set for
using the ACP Lonworks.
• IP address of the ACP Lonworks
• Gateway address
• Net mask
INSTALLING ACP LONWORKS
POWER
ON - OFF
!
CAUTION
Setting the network environment informa-
tion
If the above information is not entered,
the communication error may be occurred
or it may be impossible to control by the
ACP Lonworks. So, be careful to correctly
input.
13