Avoid - Carrier 40GKX012 703-40 Series Installation Manual

Split system "global cassette" indoor unit
Table of Contents

Advertisement

40 GKX

Avoid...

... any obstruction of the unit air intake or supply grilles.
... exposure to oil vapours.
... installation in areas with high frequency waves.
... ascending sections of condensate drain piping.
These may only be used near the unit with a maximum height
difference of 200 mm from the top of the unit.
... horizontal sections or curves of condensate drain piping with less
than 2% slope.
... exposure to direct sunshine, when the unit is operating in the
cooling mode; always use shutters or shades.
... positions too close to heating sources which may damage the unit.
... connecting condensate piping to sewage system drain without
appropriate trap. Trap height must be calculated according to the
unit discharge head in order to allow sufficient and continuous
water evacuation.
... only partial insulation of the piping.
Non-level installation which will cause condensate dripping.
MAX 200 mm
... flattening or kinking the refrigerant pipes or condensate pipes.
... excessive height difference between outdoor and indoor units
(see installation manual of outdoor unit).
E N G L I S H
GB - 5