Power supply module

Advertisement

TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
■ CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG
terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
POWER INPUT
RUN
RUN CONTACT OUTPUT
RUN
■ WIRING INSTRUCTIONS
Applicable wire size: 0.2 to 2.5 mm
Stripped length: 7 mm
(Tinning wire ends may cause contact failure and therefore
is not recommended.)
18 (0.71)
6.5 (.26)
4 5 6
1 2 3
1
U
INTERNAL
POWER
2
V
3
FG
INTERNAL
BUS
4
+
5
(AWG24 to 12)
2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
LOCKING CLAMP
90 (3.54)
CURRENT CONSUMPTION
The network module and I/O modules operate with 24 V DC
power supply via the power supply module. The total cur-
rent consumption of the network module and I/O modules
is required to be not more than the continuance output cur-
rent (400 mA) of the power supply module. If the total cur-
rent consumption exceeds the capacity of the power supply
module, change the combination of I/O modules or reduce
the number of I/O modules.
MODEL NO.
R6x-SV2
R6x-SS2
R6x-TS2
R6x-TS2A
R6x-RS2
R6x-DS1
R6x-YV2
R6x-YS2
R6x-DA4
R6x-DC4A
R6x-DC4B
R6-NC1
R6-NC3
R6-ND1
R6-NE1
R6-NE2
R6-NM1
R6-NM2
R6-NF1
R6-NP1
RUN CONTACT OUTPUT
Terminals (4 – 5) turns on in normal communications with
the host PLC.
Terminals (4 – 5) turns off in an abnormal communication
status.
R6-PSM
POSITIONING GUIDE
MAX. CURRENT (mA)
20
20
20
20
20
55
25
45
10
20
20
110
110
40
75
75
50
50
100
100
EM-7781-BZ Rev.2 P. 2 / 2