1. SPECIFICATION
ENVIRONMENTAL RAT-INGS
1.4.19 Output Disconnect: An output disconnect switch opens the negative output lead.
1.4.20 Phase Lose/Reduced Load Alarm: If for any reason the rectfffer experiences a high ripple condllicn
caused by a AC input loss an alann is actiied end the rectifiers output voltage and current will be at a
reduced level. External alarm contacts are pmvfded.
age shutdown (HVSD). ff a second HVSD occurs within five minutes of the first HVSD this cfrcuif will
shutdown and lo&out the rectifier.
I
for connection of an external DC suppfy. An external IO ampere DC supply connected to these teni-
nals will provide power to the AC contactor lf battery voltage should drop below pull-up voitage of con-
I
1.5 ENVIRONMENTAL RATfNGS
Ambient Operating Temperature Range: 0% to +SO'C (+32"F to +122'F)
Storage Temperature Range: 40°C to +85-C (40°F to +lSYF)
1 S.3
Humidity: This rectifier is capable of operating in an ambient relative humidity range of 10% to 95%.
I
noncondensing.
1.5.4
ambient temperatures of +45"C (+113'P) at 4800 feet and +fO'C (+104'P) at 7009 feet.
I
I
1.5.6 Heat Diseipeti~N 11,SSSBtWHr
1.6
ACCESSORIES: There are no accessories available for use with this rectifier.
I
1 . 7 MICELLANEOUS
1.7.1
Schematic Dlgmm: SD548502500
1.72
Wiring Diagram: T548502500
I
1.8.1
This parameter is guaranteed by Engineering Design and is not production tested