Model Data - Marconi LORAIN RHM800E50 Manual

Rectifier
Table of Contents

Advertisement

Remove the temporary insulation
3)
from the local reference leads, and
connect these leads lo the storage
terminals on circuit card A9.
g)
If the rectifier is used in charging a battery,
remove the M option capacitor assembly
from its edge connector on Regulator and
Place the POWER switch to the ON positffn.
The rectifier should start and deliver output
voltage within the range of 48 to 54 VDC.
Observe the front panel meters and indica-
tors. Verify that rectifier operation is normal
after restart.
7.18 Test Procedure 9. If. due to a prolonged AC input
power failure. the associated battery discharges to
optional customer-furnished power supply permanently
connected to terminal block TSI enables automatic
restart in this event. If an optional auxiliary power suppfy
has L@ been pennanentfy connected to TSI , a special
startup procedure is required. Perform the following
procedure to restart the rectifier in this event. This pro-
cedure will require an external 48 VDC power supply
capable of furnishing 10 amperes of current.
DANGER
If
the rectifzer is connected to battery. D
age is present at various
the rpcti~r, including the local and extended
AC voltaye
of pmducing fatal electi-
out the rectifzer. including
tact with m electrical termirtatim does not
a) Ensure that HVSD circuk breaker and
POWER switch on the rectifier are both in
the OFF position.
In the next step. observe correct polarity: oth-
erwise equipment damage may occur.
volt-
C
points thnmghout

8. MODEL DATA

input
Open the two rectifier front doors by loosen-
ing the captive fasteners and pivoting the
doors outward.
Provide an external power supply adjusted
for 48 VDC and capable of 10 amperes.
Ensure that the external power supply is
turned off.
WARNING
Connect the external power supply to tenni-
the rectifier cabinet on the rear wall. Refer
to Figure 7-4 for details. Observe correct
Place the HVSD circuit breaker and the
POWER switch to the ON poskion. The rec-
tifier should start and deliver output voltage
within the range of 48 to 54 VDC.
Observe the front panel meters and indica-
tors. Verky that rectifier operation is normal
after restart.
connect from the rectifier.
Close the rectifier front doors and secure by
tightening the captive fasteners.
This completes the low battery rectifier
restart procedure.
8.1
Refer to the Power Data Sheet for information
concerning the input and output ratings, operating limfts.
dimensions, recommended input and output lead sizes.
Section 4387
Page 37