Humidi Er - Mitsubishi Electric M Series Installation Manual

Hide thumbs Also See for M Series:
Table of Contents

Advertisement

Available languages

Available languages

13.6. Humidi er

Humidi er Control
Sequence of operation:
1. The humidistat closes CNF
2. The fan starts on high
3. CN25 provides 12VDC to turn on the Humidi er
(do not exceed 1 Watt draw per relay)
4. When the Humidistat opens, the fan continues to run for
30 seconds to clear the ductwork of moist air
5. If defrost starts during humidi er operation
CN25 de-energizes
Humidistat:
Non-Voltage a-contact input
Contact rating voltage >=15VDC
Contact Rating Current > = 0.1 A
Minimum Applicable Load =< 1mA at DC
Mode No.
Humidistat Output
16
CNF Input
OFF
1*
ON
OFF
2
ON
-
RC: Remote controller
The fan continues to run for 30 seconds after the humidi er stops.
*Factory Setting
24
max 30 ft.
Condition
(No Defrost/No Error)
Heat operation & Thermo OFF
Heat operation & Thermo ON
Heat operation & Thermo OFF
Heat operation & Thermo ON
Heat operation & Thermo OFF
Heat operation & Thermo ON
Heat operation & Thermo OFF
Heat operation & Thermo ON
-
Except for heat operation
CN25 Output
Fan Speed
OFF
RC setting
OFF
RC setting
ON
High
OFF
RC setting
ON
High
OFF
RC setting

Advertisement

Table of Contents
loading

Table of Contents