)HHGHU 7HUPLQDO DQG 0DFKLQH 7HUPLQDO
Operator's Manual
7R WHVW LQSXWV RU RXWSXWV
1. At technical level, select MAIN MENU/Tests/General/Test mode
2. Set the "Test mode" parameter to "Active" and press [E] to confirm
3. Return to the previous menu (Tests), select the input/output card to be tested and
move to the selected card menu
4. Select the parameter and enter the setting mode
5. Change the state of one or more inputs/outputs from 0 to 1 or vice versa
6. Press [E] to confirm
,5) WHVW
The user has to enter the test mode (MAIN MENU/Tests/General/Test
mode) before testing the IRF state. IRF is activated by setting the parameter
"Activate IRF" (MAIN MENU/Test/General/Activate IRF) to
"Activate IRF". This will release the IRF relay contact and send the IRF error
activated event (E57).
The test mode is cancelled by setting the "Test mode" parameter to "Not active" or
by powering up the relay. If the user does not cancel the test mode, it remains on and
the Ready LED indicator remains blinking.
/(' LQGLFDWRUV
The HMI includes three protection LED indicators. The basic functionality of the
LED indicators is described below. In addition, there are function block -specific
LED indicator operations that are described in more detail in the function block
manuals (refer to the CD-ROM Technical Descriptions of Functions, 1MRS750889-
MCD).
LED indicators can be latching or non-latching:
• Non-latching type of LED indicator goes automatically out when the fault
disappears (the protection stage resets)
• Latching type of LED indicator remains lit, although the fault disappears, until
cleared by pressing [C] for two seconds
5(B B
29