Assisting Window Messages; Help Messages - ABB REF 54 Series Operator's Manual

Hide thumbs Also See for REF 54 Series:
Table of Contents

Advertisement

1MRS 750500-MUM



)HHGHU 7HUPLQDO DQG 0DFKLQH 7HUPLQDO
Operator's Manual
$VVLVWLQJ ZLQGRZ PHVVDJHV
There are two kinds of messages that are displayed in the assisting window:
1. Indication messages that are further divided to
• information about the terminal functions and the condition of the terminal
(self-diagnosis) together with a LED indicator
• text messages without a LED indicator, generally related to e.g. condition
monitoring, alarms and warnings

2. Help messages

All messages are latching, i.e. they remain on the display until acknowledged or
overrun by another message of higher prority.
U s e C - b u t t o n t o
c l e a r E v e n t s
L
R
L
F
R
R
C
E
Uaux = 80...265 Vdc/ac
Ion = 1/5 A (Io)
fn = 50 Hz
Un = 100/110 V (U)
In = 1/5 A (I)
Uon = 100/110 V (Uo)
)LJ  3URWHFWLRQ LQGLFDWRUV
3ULRULW\ RI LQGLFDWLRQ DQG KHOS PHVVDJHV
The messages in the assisting window have a certain priority. If different type of
indications are activated simultaneously, the message with the highest priority
appears on the display. The priority of the messages is the following:
1. Internal fault
2. Trip, CBFP
3. Start, Block, Supervision (condition monitoring)
4. Help messages
As concerns the messages 1 and 2, the first active indication is shown in the assisting
window, whereas for the messages 3 and 4, the latest active indication is shown.
+HOS PHVVDJHV
Help messages (priority 4) assist the user by displaying hints on how to proceed, see
the example below.
C c l e a r s a l a r m s
E V E N T M I M I C
Assisting window
Protection indication LEDs:
Left:
Ready, IRF, Test mode
Center: Start, Block
Right:
Trip, CBFP
1MRS xxxxxx
98150
9509
5(B B