ABB REF 54 Series Operator's Manual page 13

Hide thumbs Also See for REF 54 Series:
Table of Contents

Advertisement

1MRS 750500-MUM

)HHGHU 7HUPLQDO DQG 0DFKLQH 7HUPLQDO
Operator's Manual
5. The cursor is at the first menu item, Select timeout, so you can press [E] to enter
the setting mode
6. Set the active digit (see 7. below) or press [
(range: 10...600 s)
7. Press [
] or [
] to scroll for the desired value for the digit
8. Confirm the setting by pressing [E]
The status of the corresponding object during the interlocking sequence is shown in
the assisting window. Depending on the status of the interlocking function, the open
or close command is either executed or the Interlocking LED indicator is lit if the
command is not allowed.
The control pulse type and width can be adjusted with the parameters "Fixed pulse",
"Forced pulse", "Open pulse" and "Close pulse" in MAIN MENU/Control/...(the
control function block).../Actual setting. For more information about the
open and close pulse types, please refer to the manuals of control function blocks
(CD-ROM Technical Descriptions of Functions, 1MRS750889-MCD).
7DEOH 
2EMHFW FRQWURO
6HOHFW
&ORVH
2SHQ
)UHHO\
SURJUDPPDEOH
3URJUDPPLQJ
The front panel of the terminal is provided with an optical serial communication
connector for connecting a PC to the terminal via a special RS-232 optolink cable,
type 1MKC950001-1. Additionally, a special PC program is needed for
communication between the PC and the terminal.
] to activate another digit
7R FRQWURO DQ REMHFW
1. Press the button to step through the available
objects until the desired object is highlighted
• The object remains highlighted until a control
command is given or the time-out has elapsed
2. Press [ I ] to close the selected object if it is
open
I
3. Press [O] to open the selected object if it is
closed
O
[F] button can be programmed for different
purposes
F
5(B B