Riken Keiki GD-D58-AC Operating Manual page 26

Combustible gas detector head
Table of Contents

Advertisement

4 How to Use
<Figure of Terminal Plate>
* The figure above shows GD-D58·AC.
NOTE
 Open the electric circuit lid.
Remove the electric circuit lid and display unit to find behind them the terminal plate shown in the figure
above.
Specialized tool (Option)
 Power input terminal plates are GD-D58·AC: 3-pole and GD-D58·DC: 2-pole.
 A fter use, closely tighten the lid until the thread is no longer seen (clockwise 8 rotations +1/4 rotation
or more) and the "TOP" marking faces upward. Tighten the hexagon socket set screw with a
tightening torque of 107.8±12.7 N・cm.
GD-D58 Series
Open
e
Clos
Hexagon socket set screw
GD-D58·AC
TN2
3
4
5
3
4
5
Detector head signal
GD-D58·DC
TN2
3
4
5
3
4
5
Detector head signal
Display unit
Electric circuit lid
- 26 -
4-5. How to wire
TN1
6
1
2
AC
AC
6
(L)
(N)
Pump power
supply
100 - 110
VAC
input
TN1
6
1
2
6
5
-
Pump power
supply
24 VDC
input
FG